ANUNCIAR
PSR-SPP- 24DC/ESP4/2X1/1X2 2981017 PHOENIX CONTACT Relé de segurança Ver maior
As imagens são só a título ilustrativo. Por favor, consulte a ficha técnica.

PSR-SPP- 24DC/ESP4/2X1/1X2 2981017 PHOENIX CONTACT Relé de segurança

PSR-SPP-24DC/ESP4/2X1/1X2

2981017

PHOENIX_CONTACT

Relé de segurança

Relé de segurança para aplicações SIL 3 de alta e baixa demanda, também aprovado de acordo com EN 50156, Germanischer Lloyd e EN ISO 13849, parada de emergência e monitoramento de porta de segurança, monocanal, 2 circuitos de disparo, 1 contato de advertência, largura: 22,5 mm, borne push-in plug-in

Safety relay for SIL 3 high-demand and low-demand applications, also approved in accordance with EN 50156, DNV, and EN ISO 13849, emergency stop and safety door monitoring, 1-channel, 2 enabling current paths, 1 signal contact, width: 22.5 mm, pluggable Push-in terminal block

Mais detalhes


Relés > Dispositivo de supervisão de circuitos de segurança

Segurança e Comunicações

Produto novo em sua embalagem original com todas as garantias e certificações de PHOENIX_CONTACT

Preço total: $317.34
Preço unitário: $317.34
Este preço é por unidade e mostra o valor líquido (excluindo impostos indirectos se aplicável).

Se o nosso preço não é o melhor, peça-nos uma cotação Solicitar uma cotação

Best sellers

Mais informação



Dados técnicos

Notes
Note on application
Note on applicationOnly for industrial use

Product properties
Product typeSafety relays
Product familyPSRclassic
ApplicationEmergency stop
Process technology
Safety door
Mechanical service lifeapprox. 107cycles
Relay typeElectromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Data management status
Article revision08
Times
Typical response timetyp. 60 ms (For Usmanual, monitored start)
60 ms (For Usautostart)
Typ. starting time with Us60 ms (At Us/on demand via A1)
Typical release timetyp. 20 ms (At Us/on demand via A1)
Restart time< 1 s (Boot time)
Recovery time≥ 1 s (following demand of the safety function)

Electrical properties
Maximum power dissipation for nominal condition16.12 W (At US= 26.4 V, IL² = 72 A², PTotal max= 1.72 W + 14.4 W)
Nominal operating mode100% operating factor
Air clearances and creepage distances between the power circuits
Rated insulation voltage250 V
250 V
Rated surge voltage/insulationSee section “Insulation coordination”

Input data
Digital: Logic (A1)
Description of the inputsafety-related
Number of inputs1
Input voltage range "1" signal20.4 V ... 26.4 V
Inrush currentmax. 1 A (typ. with US, Δt =
Filter timemax. 3 ms (Test pulse width of low test pulses)
min. 200 ms (Test pulse rate for low test pulse)
No brightness test pulses / high test pulses permitted.
Max. permissible overall conductor resistance50 Ω
Protective circuitSuppressor diode
Current consumption65 mA (typ. with US)
Digital: Start circuit (Y2)
Description of the inputnon-safety-related
Number of inputs1
Input voltage range "1" signal20.4 V ... 26.4 V
Inrush current< 14 mA (typically with USat Y2, Δt - 10 ms)
Filter timeNo test pulses permitted
Max. permissible overall conductor resistance50 Ω
Protective circuitSuppressor diode
Current consumption0 mA (typically with USat Y2)

Output data
Relay: Enabling current paths (13/14, 23/24)
Output description2 N/O contacts each in series, safety-related, floating
Number of outputs2
Contact switching type2 enabling current paths
Contact materialAgSnO2
Switching voltagemin. 10 V
max. 250 V AC/DC
Switching capacitymin. 100 mW
Inrush currentmin. 10 mA
max. 6 A
Switching capacity in accordance with IEC 60947-5-15 A (AC15)
5 A (DC13)
Limiting continuous current6 A (Observe derating and load limit curve)
Sq. Total current72 A2(observe derating)
Switching frequencymax. 0.5 Hz
Mechanical service life107cycles
Interrupting rating (ohmic load) max.Observe derating and load limit curve
Maximum interrupting rating (inductive load)Observe derating and load limit curve
Output fuse10 A gL/gG
4 A gL/gG (for low-demand applications)
Relay: Signaling current path (31/32)
Output description2 N/C contacts parallel, non-safety-related, floating
Number of outputs1
Contact switching type1 signaling current path
Contact materialAgSnO2
Switching voltagemin. 10 V AC/DC
max. 250 V AC/DC
Switching capacitymin. 100 mW
Inrush currentmin. 10 mA
max. 6 A
Switching capacity in accordance with IEC 60947-5-11.5 A (AC15)
2 A (DC13)
Limiting continuous current6 A
Sq. Total current36 A2(observe derating)
Switching frequencymax. 0.5 Hz
Mechanical service life107cycles
Interrupting rating (ohmic load) max.Observe derating and load limit curve
Maximum interrupting rating (inductive load)Observe derating and load limit curve
Output fuse6 A gL/gG

Connection data
Connection technology
pluggableyes
Conductor connection
Connection methodPush-in connection
Conductor cross section rigid0.2 mm² ... 1.5 mm²
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Conductor cross section, flexible, with ferrule, with plastic sleeve0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross-section AWG24 ... 16
Stripping length8 mm

Signaling
Status displayLED (green)
Operating voltage displayGreen LED

Dimensions
Width22.5 mm
Height112 mm
Depth114.5 mm

Material specifications
Color (Housing)yellow (RAL 1018)
Housing materialPolyamide

Characteristics
Safety data
Stop category0
Safety data: EN ISO 13849
Category4
Performance level (PL)e
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL)3
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL)3
Safety data: EN IEC 62061
Safety Integrity Level (SIL)3

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Min. degree of protection of inst. locationIP54
Ambient temperature (operation)-20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 70 °C
Maximum altitude≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Shock15g
Vibration (operation)10 Hz ... 150 Hz, 2g

Approvals
CE
IdentificationCE-compliant

Standards and regulations
Air clearances and creepage distances between the power circuits
Standards/regulationsDIN EN 60947-1

Mounting
Mounting typeDIN rail mounting
Mounting positionOn horizontal and vertical DIN rail

Datasheet - PDF

Avaliações: (0)

Não há comentários do produto ainda.

Adicionar avaliação
ocultar formulário
Avaliação:
Nome:
Email:
Título:
Opinión:
  Captcha
  Adicionar avaliação

Todas as classificações que recebemos a partir dos itens que oferecemos são reais e verificadas. Um pequeno gesto, mas muito valioso. Então, obrigado por esse minuto você gasta em deixar-nos a sua opinião e classificação de produtos, porque nos ajuda a continuar a melhorar e oferecer maior qualidade de serviço.