Produto adicionado com sucesso ao seu carrinho de compras
MINI MCR-SL-UI-UI-NC
2864150
PHOENIX_CONTACT
1
amplificador de isolamento 3 caminho para o isolamento elétrico de sinais analógicos, entrada / saída configurável através do interruptor DIP, com conexão a parafuso, a configuração padrão
Interface
* Produto novo em sua embalagem original com todas as garantias e certificações de PHOENIX_CONTACT
Obrigado pelo seu interesse nos nossos artigos, esperamos que o prazo indicado seja conveniente para si.
Durante a preparação do pedido pode seleccionar o tipo de envío que melhor se adapte ás suas necessidades: Aéreo Express 24Hrs, Terrestre Standard 48/72Hrs, etc.
Width | 6.2 mm |
---|---|
Height | 93.1 mm |
Depth | 102.5 mm |
Ambient temperature (operation) | -20 °C ... 65 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Degree of protection | IP20 |
Number of inputs | 1 |
---|---|
Configurable/programmable | Yes, unconfigured |
Voltage input signal | 0 V ... 10 V |
0 V ... 5 V | |
1 V ... 5 V | |
2 V ... 10 V | |
Current input signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
Max. input voltage | 30 V |
Max. input current | 50 mA |
Input resistance of voltage input | approx. 100 kΩ |
Input resistance current input | approx. 50 Ω |
Number of outputs | 1 |
---|---|
Configurable/programmable | Yes, unconfigured |
Voltage output signal | 0 V ... 10 V |
0 V ... 5 V | |
1 V ... 5 V | |
2 V ... 10 V | |
Current output signal | 0 mA ... 20 mA (please indicate if different setting when ordering) |
4 mA ... 20 mA | |
Max. output voltage | approx. 12.5 V |
Max. output current | 28 mA |
Short-circuit current | approx. 22 mA |
Load/output load voltage output | ≥ 10 kΩ |
Load/output load current output | < 500 Ω (at 20 mA) |
Nominal supply voltage | 24 V DC |
---|---|
Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
Max. current consumption | < 19 mA (Current output, at 24 V DC incl. load) |
< 9 mA (Voltage output, at 24 V DC incl. load) | |
Power consumption | < 450 mW (Current output) |
< 200 mW (Voltage output) |
Connection method | Screw connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section AWG min. | 26 |
Conductor cross section AWG max. | 12 |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Stripping length | 12 mm |
Screw thread | M3 |
No. of channels | 1 |
---|---|
Maximum transmission error | ≤ 0.1 % (of final value) |
< 0.4 % (Without adjustment) | |
Maximum temperature coefficient | < 0.01 %/K |
Temperature coefficient, typical | < 0.002 %/K |
Limit frequency (3 dB) | approx. 100 Hz |
Step response (10-90%) | approx. 3.2 ms |
Protective circuit | Transient protection |
Electrical isolation | Basic insulation according to EN 61010 |
Overvoltage category | II |
Pollution degree | 2 |
Rated insulation voltage | 50 V AC/DC |
Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Color | green |
Housing material | PBT |
Mounting position | any |
Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
Conformance | CE-compliant |
ATEX | Ex II 3 G Ex nA IIC T4 Gc X |
UL, USA / Canada | UL 508 Recognized |
Class I, Div. 2, Groups A, B, C, D T5 | |
GL | GL EMC 2 D |
Designation | Electromagnetic RF field |
---|---|
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 5 % |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 5 % |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 5 % |
Título: | Tamanho: | Tipo: |
---|---|---|
PDF CATALOG PHOENIX INTERFACE TECHNOLOGY AND SWITCHING DEVICES EN.pdf | 27 Mbytes | |
PHOENIX CONTACT-2864150-MINI MCR-SL-UI-UI-NC | 150 Kbytes |
Não há comentários do produto ainda.
Avaliação: | |
Nome: | |
Email: | |
Título: | |
Opinión: | |
Você recomendaria esse produto para comprar? | |
Adicionar avaliação |
Todas as classificações que recebemos a partir dos itens que oferecemos são reais e verificadas. Um pequeno gesto, mas muito valioso. Então, obrigado por esse minuto você gasta em deixar-nos a sua opinião e classificação de produtos, porque nos ajuda a continuar a melhorar e oferecer maior qualidade de serviço.