ANUNCIAR
PFIM-100/4/003-A 102829 Y7-102829 EATON ELECTRIC RCCB, 4P, 100A, 30 mA Ver maior
As imagens são só a título ilustrativo. Por favor, consulte a ficha técnica.

PFIM-100/4/003-A 102829 Y7-102829 EATON ELECTRIC RCCB, 4P, 100A, 30 mA

PFIM-100/4/003-A

102829

Y7-102829

EATON-MOELLER

RCCB, 4P, 100A, 30 mA

diferencial internacional pfim, 4p, 100a, 30mA, classe A

Eaton Moeller series xPole - PFIM Type AC, A, U, R RCCB. Residual current circuit breaker (RCCB), 100A, 4p, 30mA, type A

Disjuntor diferencial PFIM, 4 polos, Corrente nominal em: 100 A, Resistência nominal a curto-circuito Icn: 10 kA, Corrente nominal de falha IΔN: 0,03 A, Aparelhagem para aplicações residenciais e comerciais

Mais detalhes


Disjuntores, fusíveis > Disjuntor de corrente residual (RCCB)

Aparelhagem Modular - Industrial

Produto novo em sua embalagem original com todas as garantias e certificações de EATON-MOELLER

Preço total: $900.67
Preço unitário: $900.67
Este preço é por unidade e mostra o valor líquido (excluindo impostos indirectos se aplicável).

Se o nosso preço não é o melhor, peça-nos uma cotação Solicitar uma cotação

Best sellers

Mais informação



General specifications

Product Name
Eaton Moeller series xPole - PFIM Type AC, A, U, R RCCB
Catalog Number
102829
EAN
4015081027149
Product Length/Depth
80 mm
Product Height
76 mm
Product Width
70 mm
Product Weight
0.392 kg
Compliances
RoHS conform
Certifications
IEC/EN 61008
Model Code
PFIM-100/4/003-A

Programa de entrega

Application
Number of poles
Four-pole
Tripping time
Non-delayed
Amperage Rating
100 A
Rated short-circuit strength
10 kA
Fault current rating
30 mA
Sensitivity type
Pulse-current sensitive
Impulse withstand current
Partly surge-proof 250 A
Type
  • PFIM
  • Residual current circuit breakers
  • Type A

Dados técnicos - elétricos

Voltage rating
230 V AC / 400 V AC
Rated operational voltage (Ue) - max
400 V
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Rated fault current - min
0.03 A
Rated fault current - max
0.03 A
Frequency rating
50 Hz
Short-circuit rating
100 A (max. admissible back-up fuse)
Leakage current type
A
Rated residual making and breaking capacity
1000 A
Admissible back-up fuse overload - max
80 A gG/gL
Rated short-time withstand current (Icw)
10 kA
Surge current capacity
0.25 kA
Test circuit range
196 V AC - 264 V AC
Pollution degree
2
Lifespan, electrical
4000 operations

Dados técnicos - mecânicos

Frame
45 mm
Width in number of modular spacings
4
Built-in width (number of units)
70 mm (4 SU)
Built-in depth
70.5 mm
Mounting Method
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
DIN rail
Degree of protection
IP20, IP40 with suitable enclosure
IP20
Terminals (top and bottom)
Open mouthed/lift terminals
Terminal capacity (solid wire)
1.5 mm² - 35 mm²
Connectable conductor cross section (solid-core) - min
1.5 mm²
Connectable conductor cross section (solid-core) - max
35 mm²
Terminal capacity (stranded cable)
16 mm² (2x)
Connectable conductor cross section (multi-wired) - min
1.5 mm²
Connectable conductor cross section (multi-wired) - max
16 mm²
Terminal protection
Finger and hand touch safe, DGUV VS3, EN 50274
Busbar material thickness
0.8 mm - 2 mm
Lifespan, mechanical
20000 operations
Permitted storage and transport temperature - min
-35 °C
Permitted storage and transport temperature - max
60 °C
Climatic proofing
25-55 °C / 90-95% relative humidity according to IEC 60068-2

Verificação do design de acordo com a norma IEC/EN 61439 - dados técnicos

Rated operational current for specified heat dissipation (In)
100 A
Heat dissipation per pole, current-dependent
0 W
Equipment heat dissipation, current-dependent
18.8 W
Static heat dissipation, non-current-dependent
0 W
Heat dissipation capacity
0 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C

Verificação do design de acordo com a norma IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Informações adicionais

Accessories required
Z-HK 248432
Features
Residual current circuit breaker
Additional equipment possible
Fitted with:
Interlocking device
Special features
  • Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 1.2% for every 1 °C
  • Tripping signal contact for subsequent installation Z-NHK 248434
Used with
KLV-TC-4 276241 (Compact enclosure)
Z-FW/LP 248296 (Remote control and automatic switching device)
Z-RC/AK-4MU 101062 (sealing cover set)

ETIM for 102829 Disjuntores e fusíveis (EC000003)
Característica Valor
Número de polos (EF001391) 4
Tensão especificada de funcionamento (EF000228) 400 V
Corrente nominal especificada (EF000227) 100 A
Sensibilidade/Corrente nominal de defeito (EF002358) 0.03 A
Tensão nominal de isolamento Ui (EF001366) 440 V
Tensão estipulada suportável ao choque (Uimp) (EF011980) 4 kV
Potência dissipada (EF005387) 18.8 W
Método de montagem (EF000003) Calha DIN
Tipo de corrente de defeito diferencial (EF002560) A
Proteção seletiva (EF002561) Não
Curto retardamento (EF003604) Não
Resistência a curto-circuito (Icw) (EF002562) 10 kA
Resistência contra sobreintensidades (EF002564) 0.25 kA
Tipo de tensão (EF000187) AC
Com dispositivo de bloqueio (EF007385) Sim
Frequência de funcionamento (EF005455) 50 Hz
Possibilidade de equipamento adicional (EF008148) Sim
Grau de proteção (IP) (EF005474) IP20
Largura em número de módulos (EF002950) 4
Profundidade incorporada (EF000218) 70.5 mm
Temperatura ambiente durante a operação (EF007515) -25 °C
Grau de poluição (EF002570) 2
Secção da ligação de cabo flexível (EF007343) 1.5 mm²
Secção da ligação de cabo rígido (EF007337) 1.5 mm²
Número RAL (semelhante) (EF003882) 7035
Antideflagrante (EF004663) Não

Datasheet - PDF

Avaliações: (0)

Não há comentários do produto ainda.

Adicionar avaliação
ocultar formulário
Avaliação:
Nome:
Email:
Título:
Opinión:
  Captcha
  Adicionar avaliação

Todas as classificações que recebemos a partir dos itens que oferecemos são reais e verificadas. Um pequeno gesto, mas muito valioso. Então, obrigado por esse minuto você gasta em deixar-nos a sua opinião e classificação de produtos, porque nos ajuda a continuar a melhorar e oferecer maior qualidade de serviço.