ANUNCIAR
NZMN2-A63-NA 269222 Y7-269222 EATON ELECTRIC Interruttore automatico di potenza, 3p, 63A Visualizza ingrandito
Le immagini sono solo per fini illustrativi. Si prega di fare riferimento alla scheda tecnica p...

NZMN2-A63-NA 269222 Y7-269222 EATON ELECTRIC Interruttore automatico di potenza, 3p, 63A

NZMN2-A63-NA

269222

Y7-269222

EATON-MOELLER

Interruttore automatico di potenza, 3p, 63A

NZM-NA, 3P, 63A

Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 63A, N, frame2, A63-NA

Interruttore automatico NZM2, 3 poli, Potenza di commutazione SCCR 600Y/347 V 60 Hz( Icu ): 25 kA, Potenza di commutazione SCCR 480 V 60 Hz ( Icu ): 35 kA, Corrente nominale = corrente nominale ininterrotta (In = Iu ): 63 A, Tipo di installazione: Fisso, Collegamento a vite, Standard/Approvazione: UL/CSA, IEC, Funzione di protezione: Protezione del sistema e dei cavi

Maggiori dettagli


Apparecchi elettrici a bassa tensione > Breaker per trasformatori / generatori / impianti

Interruttori automatici con custodia modellata NZM

Prodotto nuovo nel suo imballaggio d'origine con tutte le garanzie e certificazioni de EATON-MOELLER

Prezzo totale: $571.30
Prezzo unitario: $571.30
Questo prezzo è per unità e mostra il valore netto ( escluse le imposte indirette se applicabile ).

Se il nostro prezzo non è il migliore, chiedici un preventivo Richiedi un preventivo

Related products

Più venduti

Dettagli



General specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker thermo-magnetic
Catalog Number
269222
EAN
4015082692223
Product Length/Depth
149 mm
Product Height
195 mm
Product Width
105 mm
Product Weight
2.417 kg
Compliances
RoHS conform
Certifications
UL 489
CSA-C22.2 No. 5-09
UL (Category Control Number DIVQ)
UL listed
IEC 60947-2
CSA (File No. 22086)
UL (File No. E31593)
CSA certified
CE marking
IEC
CSA (Class No. 1432-01)
IEC/EN 60947
Specially designed for North America
UL/CSA
Model Code
NZMN2-A63-NA

Specifiche del prodotto

Type
Circuit breaker
Special features
Application
  • Branch circuits, feeder circuits
  • Use in unearthed supply systems at 690 V
Amperage Rating
63 A
Voltage rating
690 V - 690 V
Circuit breaker frame type
NZM2
Features
Protection unit
Motor drive optional
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Pollution degree
3
Mounting Method
DIN rail (top hat rail) mounting optional
Built-in device fixed built-in technique
Fixed
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Equipment heat dissipation, current-dependent
20.24 W
Utilization category
A (IEC/EN 60947-2)
Isolation
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)
Ambient operating temperature - max
70 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - max
70 °C
Ambient storage temperature - min
40 °C
Low-voltage HBC fuse - max
355 A gG/gL
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Protection against direct contact
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Degree of protection
IP20 (basic degree of protection, in the operating controls area)
IP20
Direction of incoming supply
As required
Electrical connection type of main circuit
Screw connection
Lifespan, mechanical
20000 operations
Overvoltage category
III
Rated operational current
300 A (380/400 V AC-1, making and breaking capacity)
63 A (690 V AC-1, making and breaking capacity)
63 A (660-690 V AC-3, making and breaking capacity)
300 A (415 V AC-1, making and breaking capacity)
Degree of protection (IP), front side
IP66 (with door coupling rotary handle)
IP40 (with insulating surround)
Degree of protection (terminations)
IP10 (tunnel terminal)
IP00 (terminations, phase isolator and strip terminal)
Number of poles
Three-pole
Terminal capacity (copper strip)
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 10 segments of 16 mm x 0.8 mm at box terminal
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Lifespan, electrical
5000 operations at 690 V AC-3
7500 operations at 690 V AC-1
10000 operations at 400 V AC-1
6500 operations at 400 V AC-3
6500 operations at 415 V AC-3
Functions
System and cable protection
Current limiting circuit breaker
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Position of connection for main current circuit
Front side
Rated operational current for specified heat dissipation (In)
63 A
Power loss
20.2 W
Release system
Thermomagnetic release
Short-circuit total breaktime
< 10 ms
Rated short-time withstand current (t = 0.3 s)
1.9 kA
Rated short-time withstand current (t = 1 s)
1.9 kA
Short-circuit release non-delayed setting - max
630 A
Short-circuit release non-delayed setting - min
378 A
Terminal capacity (control cable)
14 mm² - 18 mm² (1x)
16 mm² - 18 mm² (2x)
Terminal capacity (copper busbar)
M8 at rear-side screw connection
Min. 16 mm x 5 mm direct at switch rear-side connection
Max. 20 mm x 5 mm direct at switch rear-side connection
Terminal capacity (copper solid conductor/cable)
6 mm² - 12 mm² (1x) at box terminal
16 mm² (1x) at tunnel terminal
6 mm² - 11 mm² (1x) direct at switch rear-side connection
Terminal capacity (aluminum solid conductor/cable)
16 mm² (1x) at tunnel terminal
Terminal capacity (copper stranded conductor/cable)
4 mm² - 3/0 mm² (1x) direct at switch rear-side connection
4 mm² - 350 mm² (1x) at tunnel terminal
4 mm² - 350 mm² (1x) at box terminal
Handle type
Rocker lever
Short delay current setting (Isd) - max
0 A
Short delay current setting (Isd) - min
0 A
Instantaneous current setting (Ii) - max
630 A
Instantaneous current setting (Ii) - min
380 A
Number of operations per hour - max
120
Overload current setting (Ir) - max
63 A
Overload current setting (Ir) - min
50 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz
85 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz
35 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz
25 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz
5 kA
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz
105 kA
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz
74 kA
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz
53 kA
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
40 kA
Standard terminals
Screw terminal
Rated operating voltage Ue (UL) - max
600Y/347 V, 480 V
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz
187 kA
Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated insulation voltage (Ui)
1000 V AC

ETIM for 269222 Apparecchi elettrici a bassa tensione (EC000228)
Caratteristica Valore
corrente permanente nominale Iu (EF001389) 63 A
tensione nominale (EF003977) 690 V
corrente limite nominale di disinserzione al corto circuito a 400 V, 50 Hz (EF007048) 50 kA
campo di corrente dell'interruttore di sovraccarico (EF002336) 50 A
intervallo di regolazione dell'attivatore di corto circuito con ritardo breve (EF007129) 0 A
intervallo di regolazione dell'attivatore di corto circuito non ritardato (EF007131) 380 A
tipologia costruttiva dell'apparecchio (EF008240) apparecchio da incasso, tecnica a installazione fissa
protezione dalle dispersioni a terra integrata (EF007296) No
tipo di collegamento circuito elettrico principale (EF006819) raccordo a vite
adatto per montaggio su guida a cappello (EF007250) No
montaggio su guida a DIN opzionale (EF008904)
numero di contatti ausiliari, contatti di riposo (EF001377) 0
numero di contatti ausiliari, contatti di chiusura (EF001376) 0
numero di contatti ausiliari, invertitori (EF003531) 0
con segnalatore di intervento presente (EF007006) No
con sganciatore di minima tensione integrato (EF001390) No
numero di poli (EF001391) 3
posizione del collegamento per circuito elettrico principale (EF006671) davanti
tipo di elemento di azionamento (EF006976) bilanciere
apparecchio completo con unità di sicurezza (EF008906)
azionamento a motore integrato (EF006697) No
azionamento a motore opzionale (EF007386)
grado di protezione (IP) (EF005474) IP20

Datasheet - PDF

Recensioni: (0)

Nessun commento per il momento.

Inserisci recensione
nascondi form
Valutazione:
Nome:
Email:
Titolo:
Testo:
  Captcha
  Inserisci recensione

Tutti i feedback che riceviamo dagli elementi che offriamo sono reali e verificati. Un piccolo gesto, ma di grande valore. Quindi grazie per quel minuto si spende in noi lasciare il vostro parere e punteggio sui prodotti, perché ci aiuta a continuare a migliorare e di offrire ancora maggiore qualità del servizio.