UVU-NZM 260154 0004358722 EATON ELECTRIC 260154 UVU-NZM View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

UVU-NZM 260154 0004358722 EATON ELECTRIC 260154 UVU-NZM

UVU-NZM

260154

0004358722

EATON-MOELLER

260154 UVU-NZM

UVU-NZM

Delay unit

More details


Low-voltage industrial components > Under voltage coil

Circuit Breakers NZM Accessories

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $518.49
Unit price: $518.49

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Often bought together

More info



Delay unit
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: combination of separate delay unit and special releases. For use with emergency switching off devices in conjunction with Emergency switching off button. Not UL/CSA approved. voltage dips of less than the setting between 0.06-16 s do not cause disconnection of the NZM circuit-breaker or N switch-disconnector. Delay time can be set: 70 ms - 4 s. With external condenser: 30.000 µF ≧ 35 V to 8 s, 90.000 µF ≧ 35 V to 16 s . A special release is required. Cannot be installed simultaneously with separate NZM..-XHIV early-make auxiliary contact or NZM..-XA.. shunt release. Delay unit for separate installation. Fixing: top-hat rail or screws. For other operating voltages use a control transformer. Can be used for: NZM1(-4), 2(-4), 3(-4), 4(-4), N(N/O)1(-4), 2(-4), 3(-4), 4(-4), 50/60 Hz 220V-240V, 380V-440V, 480V-550V, DC/AC 24 V

General specifications
Product name
Eaton Moeller series NZM release
Part no.
UVU-NZM
EAN
4015082601546
Product Length/Depth
100 millimetre
Product height
114 millimetre
Product width
74 millimetre
Product weight
0.847 kilogram
Compliances
IEC
RoHS conform
Product Tradename
NZM
Product Type
Accessories
Product Sub Type
Release
Delivery program
Type
AccessoryUndervoltage releaseUndervoltage release, off-delayed
Special features
Delay unit for combination with special undervoltage releases.For use with emergency-stop devices in connection with an emergency-stop button.not UL/CSA approvedVoltage dips of less than the setting between 0.06 – 16 s do not cause disconnection of the NZM circuit-breaker or N switch-disconnector.Delay time can be set from: 70 ms – 4 s.With additional external capacitor: 30,000 µF ≧ 35 V to 8 s, 90,000 µF ≧ 35 V to 16 s.A special release is required.Cannot be installed simultaneously with separate NZM...-XHIV early-make auxiliary contact or NZM...-XA... shunt release.Delay unit for separate installation. Fixing: top-hat rail or screws.For other operating voltages use a control transformer.
Frame
NZM1/2/3/4
Suitable for
Off-load switch
Used with
N(S)1(-4), 2(-4), 3(-4), 4(-4)
50/60 Hz
220 V - 240 V
380 V - 440 V
480 V - 550 V
DC/AC
24 V
NZM1(-4), 2(-4), 3(-4), 4(-4)N(S)1(-4), 2(-4), 3(-4), 4(-4)50/60 Hz220 V - 240 V380 V - 440 V480 V - 550 VDC/AC24 V
Technical Data - Electrical
Voltage type
AC/DC
Voltage rating at DC
24 V DC
Voltage rating at AC
220 - 550 V AC
Rated control supply voltage (Us) at AC, 50 Hz - min
24 V
Rated control supply voltage (Us) at AC, 50 Hz - max
550 V
Rated control supply voltage (Us) at AC, 60 Hz - min
24 V
Rated control supply voltage (Us) at AC, 60 Hz - max
550 V
Rated control supply voltage (Us) at DC - min
24 V
Rated control supply voltage (Us) at DC - max
24 V
Rated operation current (Ie)
< 0.5 A
Power consumption
50 VA
Delay time
70 - 4000 ms (undervoltage releases, off-delayed)
Delay time with additional external capacitor
8 s (30 mF)
16 s (90 mF)
Electric connection type
Screw connection
Technical Data - Mechanical
Number of contacts (change-over contacts)
0
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
0
Connection type
With bolt connection
Special features
Delay unit for combination with special undervoltage releases.For use with emergency-stop devices in connection with an emergency-stop button.not UL/CSA approvedVoltage dips of less than the setting between 0.06 – 16 s do not cause disconnection of the NZM circuit-breaker or N switch-disconnector.Delay time can be set from: 70 ms – 4 s.With additional external capacitor: 30,000 µF ≧ 35 V to 8 s, 90,000 µF ≧ 35 V to 16 s.A special release is required.Cannot be installed simultaneously with separate NZM...-XHIV early-make auxiliary contact or NZM...-XA... shunt release.Delay unit for separate installation. Fixing: top-hat rail or screws.For other operating voltages use a control transformer.
Technical Data - Mechanical - Terminals
Terminal capacity (solid/flexible conductor)
20 - 14 AWG (1x) at shunt release
20 - 16 AWG (2x) at shunt release
0.5 mm² - 1.5 mm² (2x) at shunt release with ferrule
0.5 mm² - 1.5 mm² (2x) for undervoltage releases, off-delayed with ferrule
0.5 mm² - 2.5 mm² (1x) at shunt release with ferrule
18 - 14 AWG (1x) for undervoltage releases, off-delayed
0.5 mm² - 2.5 mm² (1x) for undervoltage releases, off-delayed with ferrule
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional information
Functions
Delayed

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Under voltage coil (EC001022)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Undervoltage trip (ecl@ss13-27-37-04-17 [AKF015018])
Rated control supply voltage AC 50 Hz
24 - 550 V
Rated control supply voltage AC 60 Hz
24 - 550 V
Rated control supply voltage DC
24 - 24 V
Voltage type for actuating
AC/DC
Type of electric connection
Screw connection
Number of contacts as normally open contact
0
Number of contacts as normally closed contact
0
Number of contacts as change-over contact
0
Delayed
Yes
Suitable for power circuit breaker
No
Suitable for off-load switch
Yes
Suitable for motor safety switch
No
Suitable for overload relay
No

Datasheet - PDF

Title: Size: Type:
UVU-NZM 0004358722 260154 EN_260154.pdf 116 Kbytes   UVU-NZM 0004358722 260154 EN_260154.pdf

Reviews (1)

  • R Omar
    Customer rating:
  • Page:1
    Add Review
    hide form
    Rating:
    Name:
    Email:
    Subject:
    Text:
      Captcha
      Add review

    All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.