Busbar adapter, 3p, for NZM3, 630A, UL508
Type-checked busbar adapter for NZM circuit-breaker and N switch-disconnector, for surface mounting on Cu-busbars 12-30x5-10, double t and triple t profile, rated operational current Ie=630A, can be used for NZM3, PN3, N3, adapter width=140mm, rated operating voltage Ue=690VAC, screw connection on the busbar 5mm or 10mm thickness, connection top or bottom possible by turning the adapter, temperature resistant to 120 °C, self-extinguishing to UL 94, track resistance CTI 200, number of poles=3 pole, between busbar centers=60mm, can be used in conjunction with busbar system SASY 60i, UL approved, observe derating
Product name
Eaton xEffect SASY 60i MCCB adapter
Product Length/Depth
272 millimetre
Product height
35 millimetre
Product width
140 millimetre
Product weight
2.342 kilogram
Compliances
UL508A
UL CSA09 (refer to approbation report)
IEC 60439-1
CE marking
CSA-C22.2 No. 14
RoHS conform
Certifications
UL (File No. E300273)
CSA (Class No. 3211-37)
CSA (File No. 236217)
UL (Category Control Number NMTR, NMTR7)
North America (UL listed, CSA certified)
Product Tradename
xEffect SASY 60i
Product Type
Busbar system component
Product Sub Type
MCCB adapter
Catalog Notes
For surface mounting on flat copper busbars 12 – 30 x 5 – 10, double T and triple T profile
Type
60 mm system
Busbar adapters for NZM
Number of poles
Three-pole
Technical Data - Electrical
Voltage rating (UL CSA 13)
Max. 600 V AC
Voltage rating at AC
690 V AC
Rated operation current (Ie)
630 A
Electric connection type
Other
Creepage resistance
CTI 200
Technical Data - Mechanical
Degree of protection
Feeder circuits
Busbar thickness - min
5 mm
Busbar thickness - max
10 mm
Busbar adapter width
140 mm
Design verification as per IEC/EN 61439 - technical data
Temperature resistance
Up to 120 °C
Features
Self-extinguishing acc. UL 94
Functions
Busbar adapters for NZM
Current limiting circuit breaker, refer to approbation report
Component adapter for circuit breakers and switch-disconnector
Suitable for
Surface mounting on flat copper busbars 12 – 30 x 5 – 10, double T and triple T profile
Used with
N(S)3
NZM3
PN3
Feeder circuits
Busbar adapters for NZM
60 mm system
Technical data ETIM 8.0
Low-voltage industrial components (EG000017) / Busbar adapter (EC001531)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Busbar trunking system (LV circuitry) / Busbar adapter (low-voltage switching technology) (
[email protected] [ACN951011])
Mounting rail armament
None
Type of electric connection
Other
Min. busbar thickness
5 mm
Max. busbar thickness
10 mm
Width of the adapter
140 mm