S-PT-2XEX-24DC 2800040 PHOENIX CONTACT Surge protection for two floating signal circuits in screw-on module .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

S-PT-2XEX-24DC 2800040 PHOENIX CONTACT Surge protection for two floating signal circuits in screw-on module ..

S-PT-2XEX-24DC

2800040

PHOENIX_CONTACT

Available

Ship on today

Surge protection for two floating signal circuits in screw-on module with IP67 protection for sensor heads, connection M20 x 1.5. Tested in acc. with the protection types in Ex areas Ex d / Ex tD / Ex ia IIC / Ex iaD.

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection for measurement and control technology - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$186.14
2+$181.43
3+$179.09
4+$177.60
5+$177.14
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Height28 mm
Width28 mm
Depth79 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 80 °C (non-Ex)
Degree of protectionIP67

General

Housing materialHigh-grade steel
Colorsilver
Standards for cearances and creepage distancesIEC 60664-1
IEC 60079-11
Mounting typeM20
TypeScrew-in module
Number of positions4
Direction of actionLine-Line & Line-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC36 V DC
25 V AC
Maximum continuous voltage UC (wire-wire)36 V DC
25 V AC
Residual current IPE≤ 2 µA
Nominal discharge current In (8/20) µs (Core-Core)260 A
Nominal discharge current In (8/20) µs (Core-Earth)10 kA
Total surge current (8/20) µs20 kA
Total surge current (10/350) µs2 kA
Nominal pulse current Ian (10/1000) µs (Core-Core)50 A
Impulse discharge current (10/350)˽µs, peak value limp1 kA
Output voltage limitation at 1 kV/µs (Core-Core) spike≤ 65 V
Output voltage limitation at 1 kV/µs (Core-Earth) spike≤ 1.1 kV
Output voltage limitation at 1 kV/µs (Core-Core) static≤ 50 V
Voltage protection level Up (core-core)≤ 50 V (C3 - 10 A)
Voltage protection level Up (core-ground)≤ 1.1 kV (C3 - 100 A)
≤ 1.1 kV (C1 - 500 A)
≤ 1.2 kV (C2 - 10 kV / 5 kA)
Response time tA (Core-Core)≤ 1 ns
Response time tA (Core-Earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.1 dB (1 MHz / 50 Ω)
typ. 0.1 dB (400 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm systemtyp. 5 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 2 MHz
Capacity (Core-Core)typ. 1.5 nF
Capacity (Core-Earth)typ. 5 pF
Surge protection fault messageNone
Impulse durability (conductor-conductor)C3 - 25 A
Impulse durability (conductor-ground)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 100 A
D1 - 1kA
Alternating current carrying capacity (conductor-ground)10 A - 1 s

Connection data

Connection methodIndividual wires

Standards and Regulations

Standards/regulationsEN 61643-21
EN 60079-0
EN 60079-1
EN 60079-11
EN 60079-26
EN 61241-0
EN 61241-1
EN 61241-11

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2800040-S-PT-2XEX-24DCEnglish123 KbytesPHOENIX CONTACT-2800040-S-PT-2XEX-24DC

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or