Attachment plug with surge protection for 5-conductor remote bus input. Connection: 9-pos. D-SUB plug - socket. Can alternatively be snapped onto DIN rails. Incl. 1 m cable with 9-pos. D-SUB connection.

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection for information technology - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$141.19
2+$137.34
3+$135.43
4+$134.21
6+$132.74
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Height110 mm
Width25 mm
Depth63 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialZinc die-cast
Colorsilver/black
Standards for cearances and creepage distancesIEC 60664-1
VDE 0110-1
Mounting typeConnection-specific attachment plug and DIN rail, 35 mm
TypeAttachment plug for DIN rail mounting
Number of positions5
Direction of actionLine-Line & Line-Ground/Shield

Protective circuit

IEC test classificationB2
C1
C2
C3
D1
VDE requirement classB2
C1
C2
C3
D1
Maximum continuous voltage UC5.8 V DC
Maximum continuous voltage UC (wire-wire)5.8 V DC
Nominal current IN≤ 180 mA (25 °C)
Operating effective current IC at UC≤ 1 µA
Residual current IPE≤ 5 µA
Nominal discharge current In (8/20) µs (Core-Core)≤ 5 kA
Nominal discharge current In (8/20) µs (Core-Earth)≤ 5 kA
Total surge current (8/20) µs10 kA
Output voltage limitation at 1 kV/µs (Core-Earth) spike≤ 700 V
Output voltage limitation at 1 kV/µs (Core-Core) static≤ 15 V
Output voltage limitation at 1 kV/µs (Core-Earth) static≤ 700 V
Output voltage limitation at 1 kV/µs (Core-GND) static≤ 15 V
Residual voltage at In (conductor-conductor)≤ 25 V
Residual voltage at In (conductor-ground)≤ 55 V
Residual voltage at In (conductor-GND)≤ 25 V
Voltage protection level Up (core-core)≤ 16 V (B2 - 100 A)
≤ 20 V (C1 - 500 A)
≤ 20 V (C2 - 1 kA)
≤ 60 V (C2 - 5 kA)
Voltage protection level Up (core-ground)≤ 700 V (B2 - 100 A)
≤ 700 V (C1 - 500 A)
≤ 700 V (C2 - 5 kA)
Response time tA (Core-Core)≤ 1 ns
Response time tA (Core-Earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.5 dB (≤ 5 MHz / 150 Ω)
typ. 0.6 dB (≤ 10 MHz - 100/150 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ohm system≥ 100 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm system≥ 100 MHz
Capacity (Core-Core)typ. 20 pF
Resistance in seriestyp. 7 Ω
Impulse durability (conductor-conductor)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
B2 - 4 kV/100 A
Impulse durability (conductor-ground)B2 - 4 kV/100 A
C1 - 1 kV/500 A
C2 - 10 kV/5 kA
D1 - 1 kA

Connection data

Connection methodD-SUB-9
Connection type IND-SUB-9 plug
Connection type OUTD-SUB-9 socket
Connection methodRemote bus input

Connection, equipotential bonding

Connection methodCable connection

Standards and Regulations

Standards/regulationsIEC 61643-21
DIN EN 61643-21

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2800055-DT-UFB-IB-RBIEnglish113 KbytesPHOENIX CONTACT-2800055-DT-UFB-IB-RBI

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or