Key Commercial Data

Orderkey2800055
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 159 (C-4-2017)
GTIN4046356462716
Weight per Piece (excluding packing)436.000 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height110 mm
Width25 mm
Depth63 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialZinc die-cast
Colorsilver/black
Standards for cearances and creepage distancesIEC 60664-1
VDE 0110-1
Mounting typeConnection-specific attachment plug and DIN rail, 35 mm
TypeAttachment plug for DIN rail mounting
Number of positions5
Direction of actionLine-Line & Line-Ground/Shield

Protective circuit

IEC test classificationB2
C1
C2
C3
D1
VDE requirement classB2
C1
C2
C3
D1
Maximum continuous voltage UC5.8 V DC
Rated current≤ 180 mA (25 °C)
Operating effective current ICat UC≤ 1 µA
Residual current IPE≤ 5 µA
Nominal discharge current In(8/20) µs (line-line)≤ 5 kA
Nominal discharge current In(8/20) µs (line-earth)≤ 5 kA
Total discharge current Itotal(8/20) µs10 kA
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 700 V
Output voltage limitation at 1 kV/µs (line-line) static≤ 15 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 700 V
Output voltage limitation at 1 kV/µs (line-signalground) static≤ 15 V
Residual voltage at In(line-line)≤ 25 V
Residual voltage at In(line-earth)≤ 55 V
Residual voltage at In(line-signalground)≤ 25 V
Voltage protection level Up(line-line)≤ 16 V (B2 - 100 A)
≤ 20 V (C1 - 500 A)
≤ 20 V (C2 - 1 kA)
≤ 60 V (C2 - 5 kA)
Voltage protection level Up(line-earth)≤ 700 V (B2 - 100 A)
≤ 700 V (C1 - 500 A)
≤ 700 V (C2 - 5 kA)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.5 dB (≤ 5 MHz / 150 Ω)
typ. 0.6 dB (≤ 10 MHz / 100/150 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ohm system≥ 100 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm system≥ 100 MHz
Capacity (line-line)typ. 20 pF
Resistance in seriestyp. 7 Ω
Surge protection fault messagenone
Impulse durability (line-line)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
B2 - 4 kV/100 A
Impulse durability (line-earth)B2 - 4 kV/100 A
C1 - 1 kV/500 A
C2 - 10 kV/5 kA
D1 - 1 kA

Connection data

Connection methodD-SUB-9
Connection method IND-SUB-9 plug
Connection method OUTD-SUB-9 socket
Connection technologyRemote bus input

Connection, equipotential bonding

Connection methodCable connection

Standards and Regulations

Standards/regulationsIEC 61643-21
DIN EN 61643-21
Standards/specificationsDIN EN 61643-21 2002
IEC 61643-21 2000

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.