ANUNCIAR
VAL-MS 230 ST 2798844 PHOENIX CONTACT Type 2 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MS 230 ST 2798844 PHOENIX CONTACT Type 2 surge protection plug

VAL-MS 230 ST

2798844

PHOENIX_CONTACT

Type 2 surge protection plug

Plug-in type 2 surge protection with high-power varistor for VAL-MS base element, with thermal control, optical fault indication. Execution: 230 V AC

Surge protection connector type 2 with high-capacity varistor for VAL-MS base element, thermal monitoring, visual fault warning. Design: 230 V AC

More details


Earthing, lightning and surge protection > Accessories/spare parts for surge protection power supply systems

Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $85.09
Unit price: $85.09
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Often bought together

Best sellers

More info



Technical data

Product properties
Product typeReplacement plug
Product familyVALVETRAB MS
IEC test classificationII
T2
EN typeT2
IEC power supply systemTN
TT
TypeDIN rail module, two-section, divisible
Number of positions1
Surge protection fault messageoptical
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.10
Data management status
Article revision27
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal frequency fN50 Hz (60 Hz)

Connection data
Connection methodpluggable

Dimensions
Dimensional drawingesrgwravfl.jpg
Width17.5 mm
Height52.4 mm
Depth55.3 mm
Horizontal pitch1 Div.

Material specifications
Colorblack (RAL 9005)
Flammability rating according to UL 94V-0
CTI value of material600
Insulating materialPA 6.6
Material groupI
Housing materialPA 6.6

Protective circuit
Mode of protectionL-N
L-PEN
Direction of action1L-N/PE
Nominal voltage UN240/415 V AC (TN)
240/415 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC275 V AC
Residual current IPE≤ 0.45 mA
Standby power consumption PC≤ 120 mVA
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 1.35 kV
Residual voltage Ures≤ 1.35 kV (at In)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
TOV behavior at UT335 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring125 A (gG)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl)
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

Approvals
UL specifications
Maximum continuous operating voltage MCOV (L-N)275 V AC
Nominal discharge current In(L-N)20 kA
Mode of protectionL-N
Nominal voltage230 V AC
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)1910 V
SPD Type4CA

Standards and regulations
Standards/specificationsIEC 61643-11
Note2011
Standards/specificationsEN 61643-11
Note2012

Mounting
Mounting typeon base element

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.