Orderkey | 2734497 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 331 (C-8-2013) |
GTIN | 4017918974190 |
Weight per Piece (excluding packing) | 3,800.000 g |
Custom tariff number | 85389091 |
Country of origin | DE (Germany) |
Ambient temperature (operation) | 0 °C ... 55 °C |
---|---|
Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Permissible humidity (operation) | 100 % |
Permissible humidity (storage/transport) | 95 % (non-condensing) |
Air pressure (operation) | 860 hPa ... 1080 hPa (up to 1500 m above sea level) |
Air pressure (storage/transport) | 660 hPa ... 1080 hPa (up to 3500 m above sea level) |
Degree of protection | IP65/IP67 |
Supply voltage | 24 V DC |
---|---|
Supply voltage range | 18.5 V DC ... 32 V DC (including ripple) |
Ripple | 3.6 Vpp |
Designation | Mains connection |
---|---|
Connection method | POWER-COMBICON with silver contacts |
Designation connection point | Terminal strip X11 and X12 |
Number of positions | 4 |
Permissible conductor cross section | 2.5 mm² ... 4 mm² |
Operating voltage | 230 V AC ... 480 V AC ±10 % (conductor voltage) |
Max. current carrying capacity | 20 A |
Connection method | POWER-COMBICON |
---|---|
Number | 1 |
Designation connection point | X10 |
Number of positions | 8 |
Pg screw connection | Pg16 |
Operating voltage | 230 V AC ... 480 V AC |
Frequency range | 50 Hz ... 60 kHz |
Nominal current range | 0.2 A ... 8 A (parameterizable, observe derating) |
Utilization category | On the basis of AC 3 |
Switching rate | 5 cycles per minute, maximum |
Motor startup time | 1 s |
Parameterization | Via INTERBUS |
---|---|
Overspeed tripping | ≥ 40 A (after 1 second at Inom> 3.6 A) |
Continuous load current | max. 1 A |
---|---|
Type of contact | Mechanical relay contact |
Connection technology | POWER-COMBICON terminal strips |
Connection voltage | 12 V AC/DC ... 480 V AC/DC |
Input name | Digital inputs |
---|---|
Number of inputs | 6 |
Connection method | M12 connector |
Connection technology | 3, 4-wire |
Number of positions | 5 |
Input voltage | 24 V DC (DIN EN 61131-2) |
Input voltage range "0" signal | 0 V ... 5 V |
Input voltage range "1" signal | 11 V ... 30 V |
Typical input current per channel | 5 mA (for US1= 24 V) |
Filter time | 3 ms |
Power supply for sensors | UINI= US1minus 1 V 50 mA Protected against inductive reverse voltages, electronically protected against short-circuiting |
Number of outputs | 1 |
---|---|
Connection method | M12 connector |
Number of positions | 5 |
Output current | 0.5 A |
Minimum output voltage with nominal current | US1minus 2 V |
Type of protection | Electronic short-circuit/overload protection |
Mounting type | Wall mounting |
---|---|
Net weight | 3800 g |
Diagnostics messages | Mains failure, phase failure, blown fuse Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
Motor connector not plugged in, motor temperature exceeded, thermistor line short-circuited Error message in diagnostic code (bus) and display by means of the E LED on the motor starter | |
Sensor supply failure Error message in diagnostic code (bus) and display by means of the E LED on the motor starter | |
Failure of the actuator supply Error message in diagnostic code (bus) and display by means of the E LED on the motor starter | |
Motor overcurrent Error message in diagnostic code (bus) and display by means of the E LED on the motor starter | |
Output stage cannot be controlled Error message in diagnostic code (bus) and display by means of the E LED on the motor starter | |
Module error during self test Message to the master | |
Mounting type | on mounting plate |
Air clearances and creepage distances | according to EN 50178: 1998 |
---|---|
Protection class | I, IEC 61140, EN 61140, VDE 0140-1 |
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
---|---|
No hazardous substances above threshold values |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX AUTOMATION EN.pdf | 35 Mbytes | |
PHOENIX CONTACT-2734497-IBS RL 480 MLR R DIO6/1-LK2MBD | 113 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.