C-UFB-24DC 2797861 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

C-UFB-24DC 2797861 PHOENIX CONTACT Surge protection device

C-UFB-24DC

2797861

PHOENIX_CONTACT

Surge protection device

More details


Home > PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Go to successor article: C-UFB-24DC/E 2782313

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey 2797861
Packing unit 10 pc
NoteMade to Order (non-returnable)
Catalog pagePage 140 (C-6-2013)
GTIN4017918073541
Weight per Piece (excluding packing)85.730 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height93 mm
Width25.4 mm
Length25.4 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 80 °C
Degree of protectionIP20

General

Housing materialAluminum
Colorblack
Standards for cearances and creepage distancesVDE 0110-1
IEC 60664-1
Mounting typeConnection-specific intermediate plugging
TypeAttachment plug
Direction of actionLine-Shield/Earth Ground

Protective circuit

IEC test classificationC2
C3
D1
Maximum continuous voltage UC30 V DC
Maximum continuous voltage UC (line-earth)30 V DC
Nominal current IN185 mA (25 °C)
Operating effective current IC at UC≤ 10 µA
Residual current IPE≤ 10 µA
Nominal discharge current In (8/20) µs (line-earth)10 kA
Nominal discharge current In (8/20) µs (line-shield)10 kA
Total surge current (8/20) µs10 kA
Max. discharge current Imax (8/20) µs maximum (line-earth)10 kA
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 65 V
Output voltage limitation at 1 kV/µs (line-shield) spike≤ 65 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 45 V
Output voltage limitation at 1 kV/µs (line-shield) static≤ 45 V
Residual voltage at In (line-earth)≤ 45 V
Residual voltage at In (line-shield)≤ 45 V
Voltage protection level Up (line-earth)≤ 120 V (C2 - 10 kV / 5 kA)
≤ 85 V (C1 - 1 kV/500 A)
≤ 60 V (C3 - 10 A)
Voltage protection level Up (line-shield)≤ 120 V (C2 - 10 kV / 5 kA)
≤ 60 V (C3 - 10 A)
≤ 85 V (C1 - 1 kV/500 A)
Voltage protection level Up static (line-earth)≤ 50 V (C1 - 1 kV/500 A)
≤ 70 V (C2 - 10 kV / 5 kA)
Response time tA (line-earth)≤ 500 ns
Response time tA (line-shield)≤ 500 ns
Input attenuation aE, asym.2 dB (≤ 10 MHz)
Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm systemtyp. 90 MHz
Cut-off frequency fg (3 dB), asym. (shield) in 50 Ohm systemtyp. 90 MHz
Surge protection fault messagenone
Impulse durability (line-earth)C2 - 10 kV/5 kA
D1 - 2.5 kA

Connection data

Connection methodBNC 50 Ω
Connection method INBNC socket
Connection method OUTBNC plug

Connection, equipotential bonding

Connection methodScrew connection

Standards and Regulations

Standards/regulationsIEC 61643-21
Standards/specificationsIEC 61643-21 2000

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.