Standards
DIN EN 61812, IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanicalAC operated [Operations]
3 x 106
Lifespan, mechanicalDC operated [Operations]
3 x 106
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-25 - +60 °C
Ambient temperatureEnclosed
- 25 - 40 °C
Ambient temperatureStorage
- 40 - 80 °C
Mounting position
As required, except suspended
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msN/O contact
6 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msN/C contact
6 g
Degree of Protection
IP20
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Terminal capacitiesSolid
1 x (0.75 - 2.5)
2 x (0.75 - 1.5) mm2
Terminal capacitiesFlexible with ferrule
1 x (0.75 - 1.5)
2 x (0.75 - 1.5) mm2
Terminal capacitiesSolid or stranded
18 - 14 AWG
Pozidriv screwdriver
2 Size
Standard screwdriver
0.8 x 5.5
1 x 6 mm
Max. tightening torque
1.2 Nm
Rated impulse withstand voltage [Uimp]
4000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
250 V AC
Rated operational voltage [Ue]
250 V
Rated operational current [Ie]AC-15220 V 230 V 240 V [Ie]
3 A
Rated operational current [Ie]DC-13DC-13 L/R - 15 msContacts in series:1 [24 V]
1 A
Rated operational current [Ie]DC-13DC-13 L/R - 15 msContacts in series:1 [60 V]
0.2 A
Rated operational current [Ie]DC-13DC-13 L/R - 15 msContacts in series:1 [110 V]
0.2 A
Rated operational current [Ie]DC-13DC-13 L/R - 15 msContacts in series:1 [220 V]
0.1 A
Rated operational current [Ie]DC-13DC L/R ≦ 50 msContacts in series:1 [24 V]
1 A
Rated operational current [Ie]DC-13DC L/R ≦ 50 msContacts in series:1 [60 V]
0.2 A
Rated operational current [Ie]DC-13DC L/R ≦ 50 msContacts in series:1 [110 V]
0.2 A
Rated operational current [Ie]DC-13DC L/R ≦ 50 msContacts in series:1 [220 V]
0.1 A
Rated operational current [Ie]DC-13DC-13 L/R - 300 msContacts in series:1 [24 V]
1 A
Rated operational current [Ie]DC-13DC-13 L/R - 300 msContacts in series:1 [60 V]
0.2 A
Rated operational current [Ie]DC-13DC-13 L/R - 300 msContacts in series:1 [110 V]
0.2 A
Rated operational current [Ie]DC-13DC-13 L/R - 300 msContacts in series:1 [220 V]
0.1 A
Safe isolation to EN 61140between coil and auxiliary contacts
250 V AC
Safe isolation to EN 61140between the auxiliary contacts
250 V AC
Conventional thermal current [Ith]
4 A
Short-circuit rating without weldingmax. fuse
4 A gG/gL
Voltage tolerancePick-up voltageAC operated[Pick-up]
0.85 - 1.1 x Uc
Voltage tolerancePick-up voltageDC operated [Pick-up][Pick-up]
0.7 - 1.2 x Uc
Power consumption60 °C [Sealing]
2 VA
Power consumptionAC operated [Sealing]
1.8 W
Maximum operating frequencyMax. operating frequency
3600 Ops/h
Maximum operating frequencyCan be combined with auxiliary contact
360 Ops./h
Conventional thermal current Ith= IeAC-1On-delayed
< 50 ms
Conventional thermal current Ith= IeAC-1Off-delayed
< 200 ms
AC operated 50 Hz [Deviation]
< 5 %
Recovery time (after 100% time delay)
70 ms
contact changeover timeDILM32-XTEE11/DILM32-XTED11 [tu]
10 ms
contact changeover timeDILM32-XTEY20 [tu]
50 ms
Notes
For rated operational current: Making and breaking conditions to DC-13, L/R constant as stated
Max. fuses for short-circuit protection: Transparent overlay "Fuses" for time/current characteristics (please enquire)
For pick-up voltage, DC operated:Pure DC, AC bridge rectifier or smoothed double-wave rectification.
Rating data for approved types
Auxiliary contactsPilot DutyAC operated
B300
Auxiliary contactsPilot DutyDC operated
R300
Auxiliary contactsGeneral UseAC
240 V
Auxiliary contactsGeneral UseAC
5 A
Auxiliary contactsGeneral UseDC
24 V
Auxiliary contactsGeneral UseDC
5 A
Short Circuit Current RatingBasic RatingSCCR
5 kA
Short Circuit Current RatingBasic Ratingmax. Fuse
125 A
Short Circuit Current RatingBasic Ratingmax. CB
125 A
Short Circuit Current Rating480 V High FaultSCCR (fuse)
10/100 kA
Short Circuit Current Rating480 V High Faultmax. Fuse
125/70 Class J A
Short Circuit Current Rating480 V High FaultSCCR (CB)
10/65 kA
Short Circuit Current Rating480 V High Faultmax. CB
50/32 A
Short Circuit Current Rating600 V High FaultSCCR (fuse)
10/100 kA
Short Circuit Current Rating600 V High Faultmax. Fuse
125/125 Class J A
Short Circuit Current Rating600 V High FaultSCCR (CB)
10/22 kA
Short Circuit Current Rating600 V High Faultmax. CB
50/32 A