SDAINLEM(230V50HZ,240V60HZ) 051840 XTSD012A10F EATON ELECTRIC Star-delta contactor combination, 5.5kW/400V/A.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

SDAINLEM(230V50HZ,240V60HZ) 051840 XTSD012A10F EATON ELECTRIC Star-delta contactor combination, 5.5kW/400V/A..

SDAINLEM(230V50HZ,240V60HZ)

051840

XTSD012A10F

EATON-MOELLER

Star-delta contactor combination, 5.5kW/400V/AC3

More details


Contactors up to 170A

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Star-delta contactor combination, 5.5kW/400V/AC3
Star-delta contactor combination, Application: Star-delta motor starting for contactor combinations, Operating frequency: maximum 30 starts per hour, Accessories: Star-delta combinations SDAINL, Utilization category: NAC-3: Normal AC induction motors: starting, switch off during running, Rated operational current AC-3 380 V 400 V: Ie= 12 A, Max. rating for three-phase motors, 50 - 60 Hz AC-3 220 V 230 V: P= 4 kW, 380 V 400 V: P= 5.5 kW, 500 V: P= 5.5 kW, Max. changeover time: 30 s, Actuating voltage: 230 V 50 Hz, 240 V 60 Hz, Voltage AC/DC: AC operation, Individual components of the combination Mains contactor Q11: DILEM-10 + 22DILEM, Delta contactor Q15: DILEM-01 Part no., Star contactor Q13: DILEM-10 + 02DILEM Part no., Timing relay K1: DILET Part no., Notes: Also suitable for motors with efficiency class IE3., IE3-ready devices are identified by the logo on their packaging.

Delivery program

This item will continue to be available for a limited time only and is being replaced by the following item: 278286, SDAINLM12(230V50HZ,240V60HZ)
Product range
Contactor combinations
Application
Star-delta motor starting for contactor combinations
Accessories
Star-delta combinations SDAINL
Utilization category
NAC-3: Normal AC induction motors: starting, switch off during running
0000SPC-571
Notes
Also suitable for motors with efficiency class IE3.
IE3-ready devices are identified by the logo on their packaging.
Description
Operating frequency: maximum 30 starts per hour
Rated operational current [Ie]
AC-3380 V 400 V [Ie]
12 A
Max. rating for three-phase motors, 50 - 60 Hz
AC-3220 V 230 V [P]
4 kW
AC-3380 V 400 V [P]
5.5 kW
AC-3500 V [P]
5.5 kW
Max. changeover time
< 30 s
Actuating voltage
230 V 50 Hz, 240 V 60 Hz
Voltage AC/DC
AC operation
Individual components of the combination
Mains contactor Q11
DILEM-10 + 22DILEM Part no.
Delta contactor Q15
DILEM-01 Part no.
Star contactor Q13
DILEM-10 + 02DILEM Part no.
Timing relay K1
DILET Part no.
Q11
210S077

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
7 A
Heat dissipation per pole, current-dependent [Pvid]
1.21 W
Equipment heat dissipation, current-dependent [Pvid]
3.63 W
Static heat dissipation, non-current-dependent [Pvs]
4.1 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+50 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 5.0

Low-voltage industrial components (EG000017) / Starter combination (EC000010)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Combination of contactor (ecl@ss8-27-37-10-09 [AGZ572010])
Function
Star-delta contactor
Rated control supply voltage Us at AC 50HZ
230 - 230 V
Rated control supply voltage Us at AC 60HZ
240 - 240 V
Rated control supply voltage Us at DC
0 - 0 V
Voltage type for actuating
AC
Rated operation current Ie at AC-3, 400 V
12 A
Rated operation power at AC-3, 400 V
5.5 kW
Connection type main current circuit
Screw connection
Degree of protection (IP)
IP20

Characteristics

2210CON-1
Accessories
1: Overload relay

Dimensions

210X039

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.