NZM1-XSVS 109777 0004357000 EATON ELECTRIC 109777 NZM1-XSVS View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

NZM1-XSVS 109777 0004357000 EATON ELECTRIC 109777 NZM1-XSVS

NZM1-XSVS

109777

0004357000

EATON-MOELLER

109777 NZM1-XSVS

NZM1-XSVS

Socket 3p, 108A

More details


Low-voltage industrial components > Chassis part power circuit breaker

Circuit Breakers NZM Accessories

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $120.86
Unit price: $120.86

Quantity Price
1+$120.86
2+$111.78
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Socket 3p, 108A
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: for NZM circuit-breakers and N switch-disconnectors. Not UL/CSA approved. Not for Ue > 690 V. Can be used for: NZM1, N1

General specifications
Product name
Eaton Moeller series NZM plug-in unit
Part no.
NZM1-XSVS
EAN
4015081089598
Product Length/Depth
190 millimetre
Product height
78 millimetre
Product width
100 millimetre
Product weight
0.678 kilogram
Compliances
IEC
RoHS conform
Certifications
IEC/EN 60947
Product Tradename
NZM
Product Type
Accessories
Product Sub Type
Plug-in unit
Delivery program
Type
AccessoryPlug-in socket for basic unit
Number of poles
Three-pole
Nominal current
108 A
Features
Version as busbar adapter
Frame
NZM1
Technical Data - Electrical
Electrical connection type of main circuit
Frame clamp
Isolation
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts)
Direction of incoming supply
As required
Technical Data - Mechanical
Mounting Method
Plug-in unit
Mounting position
Vertical and 90° right/left
Degree of protection
IP2X (in the area of the plug-in area)
Protection against direct contact
Finger and back-of-hand proof to VDE 0106 part 100
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Technical Data - Mechanical - Terminals
Terminal equipment included
Screw connection
Design verification as per IEC/EN 61439 - technical data
Equipment heat dissipation, current-dependent
14.06 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Chassis part power circuit breaker (EC002043)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Chassis part circuit breaker (ecl@ss13-27-37-04-22 [ACN955016])
Rated current In
108 A
Number of poles
3
Version as busbar adapter
Yes
Version as built-in device
No
Type of electrical connection of main circuit
Frame clamp

Datasheet - PDF

Title: Size: Type:
NZM1-XSVS 0004357000 109777 EN_109777.pdf 111 Kbytes   NZM1-XSVS 0004357000 109777 EN_109777.pdf

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.