DUA52C724 CARLO GAVAZZI Selected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE..

DUA52C724

DUA52C724

CARLO GAVAZZI

Available

Ship on today

Selected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE 1-phase AC/DC voltage monitoring Others SIZE 17,5 mm POWER SUPPLY RANGE 8÷28 VDC MONITORING FUNCTION Under voltage for DC battery MOUTING DIN-rail INPUT RANGE 8÷28 VDC

More details


Energy Meters Control Analizers

Controls

Monitoring Relays and Measurement Current Transformers

* Brand new produt in its original packing covered by the warranties and certifications provided by CARLO GAVAZZI

QuantityPrice
1+$69.61
3+$66.22
6+$64.59
9+$63.78
12+$63.30
*This price is per unit and is the net value (not including taxes if applicable).

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Monitoring Relays DC Under Voltage Type DUA52
• DC undervoltage monitoring relay
• Measuring if power supply is below the set level
• Measures its own power supply
• Measuring ranges: 8 - 28 V DC and 38 - 58 V DC
• Adjustable hysteresis: 4 to 50%
• Output: 5 A SPDT NE relay
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• 17.5 mm housing (DIN 43880)
• LED indication for relay and power supply ON
Product Description Ordering Key
DUA 52 C 724
DUA52 is a voltage monitor- ing relay that measure its own power supply. The measuring ranges are 8-28 VDC and 38-
58 VDC. It has separate potentiometers for setpoint
and hysteresis. Typical appli- cations are monitoring of backup batteries, batteries on diesel generator sets and the like.
Housing Function Type
Item number
Output
Power supply
Type Selection
Mounting OutputMeasuring rangeSupply : 12/24 VDC Supply: 48 VDC
DIN-rail SPDT8 to 28 VDC DUA 52 C 724
DIN-rail SPDT38 to 58 VDCDUA 52 C 748
InputSpecifications
Input (voltage level)Terminals A1, A2
Measures its own power supply
Measuring ranges
DirectLevel
48 VDC 38 to 58 VDC
12 to 24 VDC 8 to 28 VDC
Output Specifications
OutputSPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO2) µ
Resistive loadsAC 1 5 A @ 250 VAC DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC DC 13 2.5 A @ 24 VDC
Mechanical life≥ 30 x 106 operations
Electrical life≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency ≤ 7200 operations/h
Dielectric strength
Dielectric voltage2 kVAC (rms) Rated impulse withstand volt. 4 kV (1.2/50 µs)
Supply Specifications
Power supplyOvervoltage cat. III Rated operational voltage(IEC 60664, IEC 60038) through terminals:
A1 and A2 724 8 to 28 VDC
748 38 to 58 VDC Dielectric voltageNone
Dielectric voltage
Supply to output 2 kV
Rated operational power 1.5 W
Specifications are subject to change without notice (08.06.10)1

Datasheet - PDF

Title:Language:Size:Type:
pdf1-mostradoSelected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE - CARLO GAVAEnglish51 Kbytespdf1-mostradoSelected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE - CARLO GAVA
pdf1-Selected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE - CARLO GAEnglish12 Mbytespdf1-mostradoSelected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE - CARLO GAVA
pdf2-mostradoSelected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE - CARLO GAVAEnglish630 Kbytespdf1-mostradoSelected parameters OUTPUT SIGNAL 1 relay SETPOINTS 1, adjustable MONITORED VARIABLE - CARLO GAVA

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review