G82113315 CARLO GAVAZZI Selected parameters Others

G82113315

CARLO GAVAZZI

Selected parameters Others

More details


Home > CARLO GAVAZZI

* Brand new product in its original packaging covered by the warranties and certifications provided by CARLO GAVAZZI

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Dupline®
Humidity and Temperature Sensor
Duline®
Type G 8211 3315
FieldbusInstallationbus
• AnaLink humidity transmitter
• Humidity range: 5 - 95% RH, precision within ± 3% RH
• AnaLink temperature transmitter
• Temperature range: 0 - 50°C, precision within ± 1°C
• Channel coding by GAP 1605
• Supplied by Dupline®
Product Description
Ordering Key
G 8211 3315
G8211 3315 is a humidity and temperature sensor for measuring relative humidity and temperature in a single room. The sensor measures the values and transmits the values to the controller G38xx xxx.
Type Selection
The transmittedvalues can beusedforventilator control e.g. in bathrooms. G8211 3315is partofthe Dupline® building automa- tion concept.
Type: Dupline® Opus housing Transmitter
3 channels
2 inputs/1 output
Humidity sensor
General Specifications
Supply ColourOrdering no.
Dupline®WhiteG 8211 3315
Input Specifications
Sensor1 integrated Humidity and Temperature sensor (Factory calibrated)
Temperature range0 to +50°C (32 to +122°F) Precision ± 1°C
Humidity range 5 - 95% RH Precision ± 3% RH
Mode of Operation
Channel programmingBy GAP 1605
No. of channels 3
Housing LK OPUS
Environment
Degree of protection IP 20
Operating temperature0 to 50 °C (32 to 122°F) Storage temperature -20 to 70°C (-4 to 158°F)
Supply Specifications
Power supplySupplied by Dupline®
Consumption
LED off< 1 mA LED on< 2.5 mA
Dimensions
Channel Programming
Using the GAP 1605 programming unit, each of the
3 channels on the sensor can be assigned any address betweenA1andP8.The
programmingsocketcan be accessed by removing the front ofthehousing.The
allocationof the channels is66 28
as follows:
Channel Description
1 Humidity channel (Analink out)
2 Temperature channel (Analink out)
3 LED control (In)
Note: Leave unwanted channels unprogrammed.
Specifications are subject to change without notice (22.12.2010) 1
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.