PHOENIX CONTACT  MINI MCR-SL-PT100-LP-NC 2810308 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

MINI MCR-SL-PT100-LP-NC 2810308 PHOENIX CONTACT Temperature measuring transducer

Reference: MINI MCR-SL-PT100-LP-NC

Code: 2810308

Manufacturer: PHOENIX CONTACT

Description:

Temperature measuring transducer
Configurable Loop-powered temperature converter for Pt 100 temperature sensors, configurable via DIP switch, with screw connection, without presetting
Configurable Loop Powered Converter for Pt 100 Temperature Sensors, DIP Switch Configurable, with Screw Connection, Not Preconfigured

Categories:

  • Sensors > Temperature transformer
  • PHOENIX CONTACT > INTERFACE Components (IF)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 196,01 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey2810308
Packing unit1 pc
Catalog pagePage 106 (C-7-2015)
GTIN4046356134668
Weight per Piece (excluding packing)68.400 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width6.2 mm
Height93.1 mm
Depth102.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 2000 m

Input data

Configurable/programmableYes, unconfigured
Sensor types (RTD) that can be usedPt 100 (IEC 60751/EN 60751)
Sensor input current1 mA (constant)
Connection technology2, 3, 4-wire

Output data

Number of outputs1
Configurable/programmableYes, unconfigured
Current output signal4 mA ... 20 mA
20 mA ... 4 mA
Max. output current23 mA (output limit)
Load/output load current output(Usupply- 12 V) / 22 mA
Ripple< 20 mVPP(at 500 Ω)

Power supply

DesignationLoop-powered
Supply voltage range12 V DC ... 30 V DC
Max. current consumption< 4.5 mA (without signal current)
Power consumption< 150 mW (without signal current)

Connection data

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.12
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Stripping length12 mm
Screw threadM3

General

Transmission error in the set measuring range((90 K / set measuring range [K]) + 0.05)%
Transmission error in the full measuring range≤ 0,25 %
Maximum temperature coefficient< 0.02 %/K
Linearity error< 0.05 % (for full measuring range)
Electrical isolationBasic insulation according to EN 61010
Overvoltage categoryII
Degree of pollution2
Rated insulation voltage30 V AC
Test voltage, input/output/supply1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Colorgreen
Housing materialPBT
Mounting positionany
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value5 %
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value5 %
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value5 %

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Connection in acc. with standardCUL
Standards/regulationsEN 61000-4-2
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
EN 61000-4-4
EN 61000-4-5
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Electrical isolationBasic insulation according to EN 61010
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

ETIM for 2810308 Sensors (EC002919)

Feature nameMeasuring range (EF001836)
Feature value-150 °C
Feature nameAnalogue output 0 mA ... 20 mA (EF006808)
Feature valueNo
Feature nameAnalogue output 4 mA ... 20 mA (EF006810)
Feature valueYes
Feature nameAnalogue output 0 V ... 2 V (EF009886)
Feature valueNo
Feature nameAnalogue output 0 V ... 5 V (EF009887)
Feature valueNo
Feature nameAnalogue output 0 V ... 10 V (EF006807)
Feature valueNo
Feature nameAnalogue output 2 V ... 10 V (EF009888)
Feature valueNo
Feature nameWith switching output (EF005225)
Feature valueNo
Feature nameModular version (EF001126)
Feature valueYes
Feature nameIntegrated configuration function (EF003064)
Feature valueYes
Feature nameEMC-version (EF001062)
Feature valueYes
Feature nameAmbient temperature (EF002386)
Feature value65 °C
Feature nameWeight (EF000167)
Feature value0.0684 kg

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.