PHOENIX CONTACT  MACX MCR-T-UI-UP-SP 2811860 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

MACX MCR-T-UI-UP-SP 2811860 PHOENIX CONTACT Temperature measuring transducer

Reference: MACX MCR-T-UI-UP-SP

Code: 2811860

Manufacturer: PHOENIX CONTACT

Description:

Temperature measuring transducer
Freely programmable temperature converter with analog output and 1 limit value relay, standard configuration, thermoresistors in 2, 3 or 4 conductor technology, thermocouples, galvanic separation, wide power range, push-in connection, SIL, PL.

Categories:

  • Sensors > Temperature transformer
  • PHOENIX CONTACT > INTERFACE Components (IF)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 507,11 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey2811860
Packing unit1 pc
Catalog pagePage 128 (C-5-2017)
GTIN4046356629119
Weight per Piece (excluding packing)150.000 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Width17.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 2000 m
Permissible humidity (operation)typ. 5 % ... 95 % (non-condensing)
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Input data

Sensor types (RTD) that can be usedPt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC)B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range-250 °C ... 2500 °C (Range depending on the sensor type)
Input signal range0 Ω ... 50 kΩ
Potentiometer resistance range0 Ω ... 50 kΩ
Input signal range-1000 mV ... 1000 mV

Output data

Configurable/programmableYes
Max. voltage output signal± 11 V
Current output signal4 mA ... 20 mA (in the case of SIL; further free configuration without SIL)
Max. current output signal22 mA
Load/output load voltage output≥ 10 kΩ
Load/output load current output≤ 600 Ω (at 20 mA)
Behavior in the event of a sensor erroraccording to NE 43 or freely configurable
Output nameRelay output
Configurable/programmableno
Contact type1 PDT
Contact materialAgSnO2, hard gold-plated
Maximum switching voltage30 V AC (30 V DC)
Maximum inrush current0.5 A (30 V AC)
1 A (30 V DC)

Power supply

Supply voltage range24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Power consumption< 1.5 W

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm
Connection methodPush-in connection

General

Maximum temperature coefficient0.01 %/K
Flammability rating according to UL 94V0
Degree of pollution2
Overvoltage categoryII
Electromagnetic compatibilityConformance with EMC directive
Housing materialPA 6.6-FR
Colorgray
DesignationInput/output/power supply
Electrical isolation300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
DesignationInput/output
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
DesignationInput/power supply
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
DesignationInput/switching output
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
ConformanceCE-compliant
ATEX II 3 G Ex nA nC ic IIC T4 Gc X
IECExEx nA nC ic IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
SIL2

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Electrical isolation4-way, between input/output/power supply/switching output
Flammability rating according to UL 94V0
ConformanceCE-compliant
ATEX II 3 G Ex nA nC ic IIC T4 Gc X
IECExEx nA nC ic IIC T4 Gc X
UL, USA/CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
DNV GL-TemperatureB
DNV GL-HumidityB
DNV GL-VibrationA
DNV GL-EMCA
DNV GL-EnclosureRequired protection according to the Rules shall be provided upon installation on board

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

ETIM for 2811860 Sensors (EC002919)

Feature nameMeasuring range (EF001836)
Feature value-250 °C
Feature nameAnalogue output 0 mA ... 20 mA (EF006808)
Feature valueNo
Feature nameAnalogue output 4 mA ... 20 mA (EF006810)
Feature valueYes
Feature nameAnalogue output 0 V ... 2 V (EF009886)
Feature valueNo
Feature nameAnalogue output 0 V ... 5 V (EF009887)
Feature valueNo
Feature nameAnalogue output 0 V ... 10 V (EF006807)
Feature valueNo
Feature nameAnalogue output 2 V ... 10 V (EF009888)
Feature valueNo
Feature nameWith switching output (EF005225)
Feature valueYes
Feature nameEMC-version (EF001062)
Feature valueYes
Feature nameAmbient temperature (EF002386)
Feature value65 °C
Feature nameWeight (EF000167)
Feature value0.15 kg

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.