OBO BETTERMANN DS-TNC M/W 5093270 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

DS-TNC M/W 5093270 OBO BETTERMANN Protection device for high-frequency cables, 130V,

Reference: DS-TNC M/W

Code: 5093270

Manufacturer: OBO BETTERMANN

Description:

Protection device for high-frequency cables, 130V,
Coaxial protection device for TNC connection: male/female. Coaxial data cable protection devices • Basic protection • High pulsed current carrying capacity 2 x 2.5 kA (10/350 µs) • Simple installation (adapter plug), m = plug/f = female connector • Various plug combinations • With TNC connector • Optimised transmission behaviour• Including OBO M25 Quick clip for simple installation

Categories:

  • Earthing, lightning and surge protection > Combined arrester for data networks/MCR-technology
  • OBO BETTERMANN > TBS Transient and lightning protection systems - OBO BETTERMANN > Surge protection, arrestor, type 3 - OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 107,88 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Arrestor monitoringno
Capacity (wire-earth)<20 pF
Capacity (wire-wire)<10 pF
CO2 Footprint (GWP) Cradle-to-Gate0,0435 kg CO2e / 1 Piece
Cut-off frequency4000 MHz
Dimension130V
Explosion-tested versionno
Impulse durability wire-earthC2: 10 kV / 5 kA (8/20µs)
Impulse durability wire-wireC2: 10 kV / 5 kA (8/20µs)
Insertion loss≤0,5 dB
Insulation resistance>1 GΩ
KategorieType 1+2 / D1+C2
Lightning impulse current2,5 kA
Lightning protection zone LPZ0→2
Maximum continuous voltage AC130 V
Maximum continuous voltage DC185 V
Nominal load current AC7 A
Nominal load current DC10 A
Number of poles1
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Plug-in systemTNC
Protection level<800 V
Protection level wire-earth<800 V
Protection level wire-wire<800 V
Protection ratingIP40
Return loss≥14 dB
ScreeningDirect
Shielding connection availableyes
Signalling on deviceNone
SPD to IEC 61643-21Class I+II / D1+C2
Telecommunications contactno
Testing standardIEC 61643-21
Total discharge current (10/350)5 kA
Total discharge current (8/20)10 kA
Wave resistance50 Ω

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.