OBO BETTERMANN V50-0-320 5093509 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

5093509 OBO BETTERMANN ARRESTER 1+2 V50-0-320

Reference: V50-0-320

Code: 5093509

Manufacturer: OBO BETTERMANN

Description:

ARRESTER 1+2 V50-0-320
Plug-in arrester V50 320 V. Combination arrester, type 1+2 • For lightning protection equipotential bonding to VDE 0185-305 (IEC 62305) • Lightning current discharge capacity of 12.5 kA (10/350) per pole • Modular, plug-in arrester with dynamic cut-off unit and visual status display • Locking mechanism with vibration protection and voltage keying • Plastic (UL 94 V-0)

Categories:

  • Earthing, lightning and surge protection > Combined arrester for power supply systems
  • OBO BETTERMANN > TBS Transient and lightning protection systems - OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 87,45 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

ApprovalsVDE, KEMA, UL, ÖVE
Blow-outno
CO2 Footprint (GWP) Cradle-to-Gate0,2308 kg CO2e / 1 Piece
Conductor cross-section, flexible (fine-wire), max.2 AWG
Conductor cross-section, flexible (fine-wire), max.35 mm²
Conductor cross-section, flexible (fine-wire), min.1,5 mm²
Conductor cross-section, flexible (fine-wire), min.16 AWG
Conductor cross-section, rigid (single-wire/multiwire), max.35 mm²
Conductor cross-section, rigid (single-wire/multiwire), max.2 AWG
Conductor cross-section, rigid (single-wire/multiwire), min.16 AWG
Conductor cross-section, rigid (single-wire/multiwire), min.1,5 mm²
Connection cross-section, FM terminals, max.1,5 mm²
Connection cross-section, FM terminals, max.16 AWG
Connection cross-section, FM terminals, min.0,5 mm²
Connection cross-section, FM terminals, min.21 AWG
Dimension320V
Housing material surge protection componentsPA UL 94 V-0
Installation typeDIN rail 35 mm
Integrated back-up fuseno
Lightning surge current (10/350 μs)12,5 kA
Max. mains-side overcurrent protection160 A gL/gG
Maximum back-up fuse160 A
Maximum continuous voltage (L-N)320 V
Maximum continuous voltage AC320 V
Maximum discharge current (8/20 μs)50 kA
Maximum discharge current (8/20 μs) [L-N]50 kA
Minimum distance1,5 mm
Network formAll
Nominal discharge current (8/20 µs)30 kA
Nominal discharge current (8/20 µs) [L-N]30 kA
Nominal voltage AC (50/60 Hz)230 V
Operating temperature, max.80 °C
Operating temperature, min.-40 °C
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Pole number1
Pole version1
Protection level [L-N]≤1,4
Protection ratingIP20
Remote signallingno
Residual voltage [L-N] @ 1 kA0,9 kV
Residual voltage [L-N] @ 12.5 kA1,1 kV
Residual voltage [L-N] @ 5 kA1 kV
Response time<25 ns
Short-circuit resistance for max. mains-side overcurrent protection50 kA eff
Signalling on deviceVisual
SPD to EN 61643-11Type 1+2
SPD to IEC 61643-1Class I+II
SPD to UL 1449Type 4
Torque4 Nm
TOV voltage [L-N] ‒ fail safe mode ‒ 120 min.440 V
TOV voltage [L-N] ‒ withstand mode ‒ 5 s335 V

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.