Standards
General requirements: IEC/EN 61800-2
EMV requirements: IEC/EN 61800-3
Safety requirements: IEC/EN 61800-5-1:2007/A1:2017; UL 61800-5-1:2012 (Rev. 2018), CSA C22.2 No. 274-17:2017
Certifications
CE, UL, cUL, c-Tick, UkrSEPRO, EAC
Production quality
RoHS, ISO 9001
Climatic proofing [ρw]
< 95%, average relative humidity (RH), non-condensing, non-corrosive %
Ambient temperatureOperating ambient temperature min.
-10 °C
Ambient temperatureOperating ambient temperature max.
+50 °C
Ambient temperatureoperation (110 % overload) [ϑ]
-10 - +40 (max. +55 with 1 % derating per Kelvin temperature rise) °C °C
Ambient temperature
Operation with 110 % overload (1 min./10 min.): -10 to +40 (max. +55 with 1% derating per Kelvin above limit)
Operation with 150% overload (1 min./10 min.): -10 to +50 (max. +60 with 1% derating per Kelvin above limit)
-20 with cold-weather mode
Ambient temperatureStorage [ϑ]
-40 - +70 °C
Radio interference levelRadio interference class (EMC)
C1 (with external filter, for conducted emissions only), C2, C3, depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Radio interference levelEnvironment (EMC)
1st and 2nd environments as per EN 61800-3
Radio interference levelmaximum motor cable length [I]
C2 ≤ 5 m
C3 ≤ 25 m m
Mechanical shock resistance
EN 61800-5-1, EN 60068-2-6: 10 - 150 Hz
Amplitude: 0,75 mm (peak) bei 10 - 57 Hz
Maximum acceleration amplitude: 1 g at 57 – 150 Hz g
Mounting position
Vertical
Altitude
0 - 1000 m above sea level
Above 1000 m: 1% derating for every 100 m
max. 3000 m (2000 m for Corner Grounded TN Systems) m
Degree of Protection
IP20/NEMA0
Protection against direct contact
BGV A3 (VBG4, finger- and back-of-hand proof)
SupplyRated operational voltage [Ue]
230 V AC, 1-phase
240 V AC, single-phase
SupplyMains voltage (50/60Hz) [ULN]
208 (-10%) - 240 (+10%) V
SupplyInput current (150% overload) [ILN]
12.7 A
SupplyInput current (110% overload) [ILN]
20.1 A
SupplySystem configuration
TN-S, TN-C, TN-C-S, TT, IT
SupplySupply frequency [fLN]
50/60 Hz
SupplyFrequency range [fLN]
45–66 (± 0%) Hz
SupplyMains switch-on frequency
Maximum of one time every 60 seconds
SupplyMains current distortion [THD]
40 %
SupplyRated conditional short-circuit current [Iq]
< 100 kA
Power sectionFunction
Variable frequency drive with internal DC link, DC link choke and IGBT inverter
Power sectionOverload current (150% overload) [IL]
16.5 A
Power sectionOverload current (110% overload) [IL]
19.25 A
Power sectionmax. starting current (High Overload) [IH]
200 %
Power sectionNote about max. starting current
for 2 seconds every 20 seconds
Power sectionOutput voltage with Ve[U2]
230 V AC, 3-phase
240 V AC, 3-phase
Power sectionOutput Frequency [f2]
0 - 50/60 (max. 400) Hz
Power sectionSwitching frequency [fPWM]
4
adjustable 1 - 16 kHz
Power sectionOperation Mode
U/f control
Speed control with slip compensation
sensorless vector control (SLV)
Torque regulation
PM motors
Power sectionFrequency resolution (setpoint value) [Δf]
0.01 Hz
Power sectionRated operational currentAt 150% overload [Ie]
11 A
Power sectionRated operational currentAt 110% overload [Ie]
17.5 A
Power sectionNote
Rated operational current for a switching frequency of 1 - 16 kHz and an ambient temperature of +50 °C for a 150% overload and +40 °C for a 110% overload
Power sectionMotor current limit [I]
0.1 - 2 x IH(CT) A
Power sectionPower lossHeat dissipation at rated operational current Ie=150 % [PV]
0 W
Power sectionPower lossHeat dissipation at rated operational current Ie=110% [PV]
0 W
Power sectionHeat dissipation at current/speed [%]Current = 100%Speed = 0 % [PV]
122.2 W
Power sectionHeat dissipation at current/speed [%]Current = 100%Speed = 50 % [PV]
70.2 W
Power sectionHeat dissipation at current/speed [%]Current = 100%Speed = 90 % [PV]
197.7 W
Power sectionHeat dissipation at current/speed [%]Current = 50 %Speed = 0 % [PV]
161.8 W
Power sectionHeat dissipation at current/speed [%]Current = 50 %Speed = 50 % [PV]
85.8 W
Power sectionHeat dissipation at current/speed [%]Current = 50 %Speed = 90 % [PV]
92.8 W
Power sectionHeat dissipation at current/speed [%]Current = 50 %Speed = 0 % [PV]
56 W
Power sectionHeat dissipation at current/speed [%]Current = 50 %Speed = 50 % [PV]
46.4 W
Power sectionFan
temperature controlled
Power sectionInternal fan delivery rate
42 m3/h
Power sectionFitted with
Radio interference suppression filter
7-digital display assembly
Setpoint potentiometer
Brake chopper
Power sectionSafety function
STO (Safe Torque Off, SIL2, PLd Cat 3)
Power sectionFrame size
FS2
Motor feederNote
for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz
for PM motors
Motor feederNote
Overload cycle for 60 s every 600 s
Motor feederNote
at 230 V, 50 Hz
Motor feeder150 % Overload [P]
2.2 kW
Motor feeder110 % Overload [P]
4 kW
Motor feederNote
at 230 V, 60 Hz
Motor feeder150 % Overload [P]
3 HP
Motor feeder110 % Overload [P]
5 HP
Motor feederBraking functionStandard braking torque
max. 30 % MN
Motor feederBraking functionDC braking torque
adjustable to 150 %
Motor feederBraking functionBraking torque with external braking resistance
Max. 100% of rated operational current Iewith external braking resistor
Motor feederBraking functionminimum external braking resistance [Rmin]
16 Ω
Motor feederBraking functionDC braking [%]
≦ 150, adjustable I/Ie
External control voltage [Uc]
24 V DC (max. 100 mA options incl.) V
Reference voltage [Us]
10 V DC (max. 10 mA) V
Analog inputs
1, can be parameterized, 0–10 V DC, 2–10 V DC, 0/4–20 mA
Analog outputs
1, parameterizable, 0 - 10 V
Digital inputs
4, parameterizable, max. 30 V DC
Relay outputs
2, parameterizable, 1 changeover contacts and 1 N/O, 3 A (240 VAC) / 3 A (24 VDC)
Interface/field bus (built-in)
Modbus RTU
Modbus TCP
BACnet MS/TP
Ethernet IP
BACnet TCP
Assigned switching and protective elements
Power WiringSafety device (fuse or miniature circuit-breaker)IEC (Type B, gG), 150 %
PKZM0-12
Power WiringSafety device (fuse or miniature circuit-breaker)IEC (Type B, gG), 110 %
PKZM0-20
Power WiringSafety device (fuse or miniature circuit-breaker)UL (Class CC or J)
25 A
Power WiringMains contactor150 % overload (CT/IH, at 50 °C)
DILM7-10 (230V50HZ,240V60HZ)
Power WiringMains contactor110 % overload (VT/IL, at 40 °C)
DILM7-10 (230V50HZ,240V60HZ)
Power WiringMain choke150 % overload (CT/IH, at 50 °C)
DX-LN1-013
Power WiringMain choke110 % overload (VT/IL, at 40 °C)
DX-LN1-024
Power WiringRadio interference suppression filter (external, 150 %)
DX-EMC12-014-FS1
Power WiringRadio interference suppression filter (external, 110 %)
DX-EMC12-025-FS2
Power WiringNote regarding radio interference suppression filter
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
DC link connectionBraking resistance10 % duty factor (DF)
DX-BR022-1K4
DC link connectionBraking resistance20 % duty factor (DF)
DX-BR022-1K4
DC link connectionBraking resistance40 % duty factor (DF)
DX-BR022-1K4
Motor feedermotor choke150 % overload (CT/IH, at 50 °C)
DX-LM3-011
Motor feedermotor choke110 % overload (VT/IL, at 40 °C)
DX-LM3-035
Motor feederSine filter150 % overload (CT/IH, at 50 °C)
DX-SIN3-016
Motor feederSine filter110 % overload (VT/IL, at 40 °C)
DX-SIN3-023
Motor feederAll-pole sine filter150 % overload (CT/IH, at 50 °C)
DX-SIN3-013-A
Motor feederAll-pole sine filter110 % overload (VT/IL, at 40 °C)
DX-SIN3-024-A