ANUNCIAR
NZMS3-AE630-T-AVE 113597 Y7-113597 EATON ELECTRIC Interr. autom. pot. 630A 3p protez. imp./c. disp. terra+ri.. Visualizza ingrandito
Le immagini sono solo per fini illustrativi. Si prega di fare riferimento alla scheda tecnica p...

NZMS3-AE630-T-AVE 113597 Y7-113597 EATON ELECTRIC Interr. autom. pot. 630A 3p protez. imp./c. disp. terra+ri..

NZMS3-AE630-T-AVE

113597

Y7-113597

EATON-MOELLER

Interr. autom. pot. 630A 3p protez. imp./c. disp. terra+ritraib.

Int. Auto NZM, 3P 630 A Interruttore automatico, protezione

Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker 3-pole 630A, system/cable protection+earth-fault protection, withdrawable unit

Serie NZM.. -Gli interruttori automatici AE coprono tutti i casi applicativi con solo quattro dimensioni compatte e sono adatti per il mercato IEC. I gruppi funzionali modulari rendono sempre flessibile il montaggio. Con attuatori elettronici per impianti e protezione cavi. Note: Misura RMS e memoria termica

Maggiori dettagli


Apparecchi elettrici a bassa tensione > Breaker per trasformatori / generatori / impianti

Interruttori automatici con custodia modellata NZM

Prodotto nuovo nel suo imballaggio d'origine con tutte le garanzie e certificazioni de EATON-MOELLER

Prezzo totale: $5,217.65
Prezzo unitario: $5,217.65
Questo prezzo è per unità e mostra il valore netto ( escluse le imposte indirette se applicabile ).

Se il nostro prezzo non è il migliore, chiedici un preventivo Richiedi un preventivo

Più venduti

Dettagli



General specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker electronic
Catalog Number
113597
EAN
4015081131228
Product Length/Depth
346 mm
Product Height
260 mm
Product Width
185 mm
Product Weight
11.313 kg
Compliances
RoHS conform
Certifications
IEC/EN 60947
IEC
Model Code
NZMS3-AE630-T-AVE

Dati tecnici - elettrici

Voltage rating
690 V - 690 V
Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated short-time withstand current (t = 0.3 s)
3.3 kA
Rated short-time withstand current (t = 1 s)
3.3 kA
Amperage Rating
630 A
Instantaneous current setting (Ii) - min
1260 A
Instantaneous current setting (Ii) - max
5040 A
Overload current setting (Ir) - min
315 A
Overload current setting (Ir) - max
630 A
Short delay current setting (Isd) - min
0 A
Short delay current setting (Isd) - max
0 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz
100 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
70 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz
65 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz
18 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz
6 kA
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz
220 kA
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz
154 kA
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz
143 kA
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz
80 kA
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
50 kA
Short-circuit total breaktime
< 10 ms
Electrical connection type of main circuit
Screw connection
Isolation
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)
Number of operations per hour - max
60
Handle type
Rocker lever
Utilization category
A (IEC/EN 60947-2)
Overvoltage category
III
Pollution degree
3
Lifespan, electrical
2000 operations at 690 V AC-3
5000 operations at 400 V AC-1
2000 operations at 415 V AC-3
3000 operations at 690 V AC-1
2000 operations at 400 V AC-3
5000 operations at 415 V AC-1
Direction of incoming supply
As required

Dati tecnici - comunicazione

Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated short-time withstand current (t = 0.3 s)
3.3 kA
Rated short-time withstand current (t = 1 s)
3.3 kA
Amperage Rating
630 A
Instantaneous current setting (Ii) - min
1260 A
Instantaneous current setting (Ii) - max
5040 A
Overload current setting (Ir) - min
315 A
Overload current setting (Ir) - max
630 A
Short delay current setting (Isd) - min
0 A
Short delay current setting (Isd) - max
0 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz
100 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
70 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz
65 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz
18 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz
6 kA
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz
220 kA
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz
154 kA
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz
143 kA
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz
80 kA
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
50 kA
Short-circuit total breaktime
< 10 ms
Electrical connection type of main circuit
Screw connection
Isolation
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)
Number of operations per hour - max
60
Handle type
Rocker lever
Utilization category
A (IEC/EN 60947-2)
Overvoltage category
III
Pollution degree
3
Lifespan, electrical
2000 operations at 690 V AC-3
5000 operations at 400 V AC-1
2000 operations at 415 V AC-3
3000 operations at 690 V AC-1
2000 operations at 400 V AC-3
5000 operations at 415 V AC-1
Direction of incoming supply
As required

Dati tecnici - meccanici

Mounting Method
Withdrawable
Built-in device slide-in technique (withdrawable)
Degree of protection
IP20 (basic degree of protection, in the operating controls area)
IP20
Degree of protection (IP), front side
IP66 (with door coupling rotary handle)
IP40 (with insulating surround)
Degree of protection (terminations)
IP10 (tunnel terminal)
IP00 (terminations, phase isolator and strip terminal)
Protection against direct contact
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Position of connection for main current circuit
Back side
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Lifespan, mechanical
15000 operations

ETIM for 113597 Apparecchi elettrici a bassa tensione (EC000228)
Caratteristica Valore
corrente permanente nominale Iu (EF001389) 630 A
tensione nominale (EF003977) 690 V
corrente limite nominale di disinserzione al corto circuito a 400 V, 50 Hz (EF007048) 70 kA
campo di corrente dell'interruttore di sovraccarico (EF002336) 315 A
intervallo di regolazione dell'attivatore di corto circuito con ritardo breve (EF007129) 0 A
intervallo di regolazione dell'attivatore di corto circuito non ritardato (EF007131) 1260 A
tipologia costruttiva dell'apparecchio (EF008240) apparecchio da incasso, tecnica a innesto
protezione dalle dispersioni a terra integrata (EF007296)
tipo di collegamento circuito elettrico principale (EF006819) raccordo a vite
adatto per montaggio su guida a cappello (EF007250) No
montaggio su guida a DIN opzionale (EF008904) No
numero di contatti ausiliari, contatti di riposo (EF001377) 0
numero di contatti ausiliari, contatti di chiusura (EF001376) 0
numero di contatti ausiliari, invertitori (EF003531) 0
con segnalatore di intervento presente (EF007006) No
con sganciatore di minima tensione integrato (EF001390) No
numero di poli (EF001391) 3
posizione del collegamento per circuito elettrico principale (EF006671) dietro
tipo di elemento di azionamento (EF006976) bilanciere
apparecchio completo con unità di sicurezza (EF008906)
azionamento a motore integrato (EF006697) No
azionamento a motore opzionale (EF007386)
grado di protezione (IP) (EF005474) IP20

Datasheet - PDF

Recensioni: (0)

Nessun commento per il momento.

Inserisci recensione
nascondi form
Valutazione:
Nome:
Email:
Titolo:
Testo:
  Captcha
  Inserisci recensione

Tutti i feedback che riceviamo dagli elementi che offriamo sono reali e verificati. Un piccolo gesto, ma di grande valore. Quindi grazie per quel minuto si spende in noi lasciare il vostro parere e punteggio sui prodotti, perché ci aiuta a continuare a migliorare e di offrire ancora maggiore qualità del servizio.