P3-63/I3/SVB/N 207341 EATON ELECTRIC Interrupteur général, +coffret, 3p+N, 63A, poignée rouge-jaune, verroui.. Agrandir l'image
Les images sont à titre illustratif. Svp, révisez la fiche technique.

P3-63/I3/SVB/N 207341 EATON ELECTRIC Interrupteur général, +coffret, 3p+N, 63A, poignée rouge-jaune, verroui..

P3-63/I3/SVB/N

207341

EATON-MOELLER

Interrupteur général, +coffret, 3p+N, 63A, poignée rouge-jaune, verrouillable

Interrupteur général; 3-pôles + N; 63; boîtier de Montage; Poignée Rouge/Jaune Verrouillable sur la position 0 (ARRÊT)

Eaton Moeller® series P3 On-Off switch, P3, 63 A, surface mounting, 3 pole + N, Emergency switching off function, With red rotary handle and yellow locking ring, Lockable in the 0 (Off) position

Plus de détails


Sectionneurs et commutateurs à cames

* Produit neuf dans son emballage d'origine avec toutes les garanties et les certifications émises par EATON-MOELLER

Prix total: $182.11
Prix unitaire: $182.11

Quantité Prix
1+$182.11
2+$164.50
*Ce prix est par unité et montre la valeur nette (excluant les taxes indirectes le cas échéant) .

Si notre prix n'est pas le meilleur, demandez-nous un devis. Demander un devis

Les plus vendus

En savoir plus



Spécifications générales

Product Name
Eaton Moeller® series P3 Main switch
Catalog Number
207341
Model Code
P3-63/I3/SVB/N
EAN
4015082073411
Product Length/Depth
160 mm
Product Height
222 mm
Product Width
120 mm
Product Weight
0.978 kg
Compliances
CE

Features & Functions

Features
Version as emergency stop installation
Version as main switch
Version as maintenance-/service switch
Fitted with:
Red rotary handle and yellow locking ring
Functions
Emergency switching off function
Interlockable
Locking facility
Lockable in the 0 (Off) position
Number of poles
Four-pole

General

Accessories
Auxiliary contact fitted by user.
Degree of protection
NEMA 12
Degree of protection (front side)
IP65
Mounting method
Surface mounting
Product Category
On-Off switch
Suitable for
Ground mounting

Electrical rating

Rated operational power at AC-3, 380/400 V, 50 Hz
30 kW
Rated operational power at AC-23A, 400 V, 50 Hz
37 kW
Rated operational voltage (Ue) at AC - max
690 V
Rated uninterrupted current (Iu)
63 A
Uninterrupted current
Rated uninterrupted current Iu is specified for max. cross-section.

Short-circuit rating

Rated conditional short-circuit current (Iq)
4 kA (Load side)
100 kA (Supply side)
Rated short-time withstand current (Icw)
1.26 kA

Contacts

Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0

Actuator

Actuator color
Red
Actuator type
Other

Design verification

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
UV resistance only in connection with protective shield.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Datasheet - PDF

Commentaires: (0)

Aucun commentaire sur le produit encore.

Écrire commentaire
Sous forme de peau
Score:
Nom:
Email:
Titre:
Commentaire:
  Captcha
  Écrire commentaire

Toutes les évaluations que nous recevons des articles que nous proposons sont réels et vérifiés. Un petit geste, mais très précieux. Je vous remercie pour cette minute que vous passez à nous laisser votre avis et note sur les produits, car il nous aide à continuer à améliorer et à offrir encore plus la qualité de service.