PHOENIX CONTACT  VAL-MS 350 VF-RW ST 1050280 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MS 350 VF-RW ST 1050280 PHOENIX CONTACT Type 2 surge protection plug

Reference: VAL-MS 350 VF-RW ST

Code: 1050280

Manufacturer: PHOENIX CONTACT

Description:

Type 2 surge protection plug
Plug-in type 2 surge protection with varistor series connection and gas-filled arc arrester for VAL-MS base element, with thermal control, optical fault indication. Version: 350 V AC with increased lightning current shunt capability.

Categories:

  • Earthing, lightning and surge protection > Accessories/spare parts for surge protection power supply systems
  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • Reviews
Guarantee, repair and return.

Unit Price: 82,20 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey1050280
Packing unit10 pc
Minimum order quantity10 pc
NoteMade to Order (non-returnable)
GTIN4055626665177
Weight per Piece (excluding packing)47.430 g
Custom tariff number85363090
Country of originDE (Germany)

Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
Mode of protectionL-N
L-PE
L-PEN
Mounting typeon base element
Colorjet black RAL 9005
Housing materialPA 6.6
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions1
Surge protection fault messageoptical

Additional descriptions

NoteUsable in all low-voltage systems between L-N or L-PEN.
Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE= RAaccordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a)

Protective circuit

Nominal voltage UN240/415 V AC (TN)
240/415 V AC (TT)
230 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC350 V AC
Residual current IPE≤ 5 µA
Standby power consumption PC≤ 2 mVA
Nominal discharge current In(8/20) µs10 kA
Maximum discharge current Imax(8/20) µs20 kA
Impulse discharge current (10/350) µs, charge1.25 As
Impulse discharge current (10/350) µs, specific energy1.56 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp2.5 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures≤ 1.35 kV (at In)
≤ 1.35 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 1.5 kV
TOV behavior at UT415 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
Response time tA≤ 100 ns
Max. backup fuse with branch wiring125 A (gG)

Connection data

Connection methodpluggable

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications

DATASHEET - PDF

Title
Size
Type

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.