PHOENIX CONTACT  TT-UKK5-M/ 48DC 2795973 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

TT-UKK5-M/ 48DC 2795973 PHOENIX CONTACT Surge protection device

Reference: TT-UKK5-M/ 48DC

Code: 2795973

Manufacturer: PHOENIX CONTACT

Description:

Surge protection device

Categories:

  • Earthing, lightning and surge protection > Surge protection device for data networks/MCR-technology
  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey2795973
Packing unit50 pc
NoteMade to Order (non-returnable)
Catalog pagePage 99 (C-6-2013)
GTIN4017918073237
Weight per Piece (excluding packing)25.590 g
Custom tariff number85363010
Country of originGR (Greece)

Dimensions

Height80 mm
Width6.2 mm
Depth68 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialPA
Flammability rating according to UL 94V-2
Colorblack
Standards for cearances and creepage distancesVDE 0110-1
Mounting typeDIN rail: 35 mm
TypeDouble-level terminal block with disconnect knife
Number of positions1
Direction of actionLine-Line

Protective circuit

IEC test classificationC3
VDE requirement classC3
Nominal voltage UN48 V DC
Maximum continuous voltage UC53 V DC
37 V AC
Rated current12 A (45°C)
Operating effective current ICat UC≤ 5 µA
Nominal discharge current In(8/20) µs (line-line)90 A
Total discharge current Itotal(8/20) µs90 A
Max. discharge current Imax(8/20) µs maximum (line-line)90 A
Nominal pulse current Ian (10/1000) µs (line-line)17.7 A
Output voltage limitation at 1 kV/µs (line-line) static≤ 80 V
Residual voltage at In(line-line)≤ 111 V
Response time tA(line-line)≤ 1 ns
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 3.8 MHz
Capacity (line-line)≤ 0.85 nF
Surge protection fault messagenone
Impulse durability (line-line)C3 - 10 A

Connection data

Connection methodScrew connection
Connection method INScrew terminal blocks
Connection method OUTScrew terminal blocks
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 4 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/regulationsIEC 61643-21
Standards/specificationsIEC 61643-21 2000
DIN EN 61643-21 2002

Classifications

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.