PHOENIX CONTACT  TT-UK5/ 48DC 2794709 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

TT-UK5/ 48DC 2794709 PHOENIX CONTACT Surge protection device

Reference: TT-UK5/ 48DC

Code: 2794709

Manufacturer: PHOENIX CONTACT

Description:

Surge protection device
Terminal block with fine surge protection between the active part and the rail, nominal voltage: 48 V DC, installation on NS 32 or NS 35/7.5, terminal width: 6.2 mm, terminal height: 47 mm

Categories:

  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey2794709
Packing unit50 pc
NoteMade to Order (non-returnable)
Catalog pagePage 98 (C-6-2013)
GTIN4017918072889
Weight per Piece (excluding packing)1.150 g
Custom tariff number85363030
Country of originGR (Greece)

Dimensions

Height47 mm
Width6.2 mm
Length42.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialPA
Flammability rating according to UL 94V-2
Colorblack
Mounting typeDIN rail: 35 mm
TypeSingle-level terminal block
Number of positions1
Direction of actionLine-Earth Ground

Protective circuit

IEC test classificationC3
VDE requirement classC3
Nominal voltage UN48 V DC
Maximum continuous voltage UC53 V DC
37 V AC
Rated current32 A (50 °C)
Residual current IPE≤ 5 µA
Nominal discharge current In(8/20) µs (line-earth)90 A (per path)
Total surge current (8/20) µs90 A
Max. discharge current Imax(8/20) µs maximum (line-earth)90 A
Nominal pulse current Ian (10/1000) µs (line-earth)17.7 A
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 80 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 80 V
Residual voltage at In(line-earth)≤ 111 V
Response time tA(line-earth)≤ 1 ns
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm systemtyp. 3.8 MHz
Capacity (line-earth)≤ 0.85 nF
Surge protection fault messagenone
Impulse durability (line-earth)C3 - 10 A

Connection data

Connection methodScrew connection
Connection method INScrew terminal blocks
Connection method OUTScrew terminal blocks
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 4 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/regulationsIEC 61643-21

Environmental Product Compliance

REACh SVHC4-Nonylphenol, ethoxylated
Lead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

DATASHEET - PDF

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.