Overvoltage protection. in IP67 screw-on module for measuring probes, direct mounting via 3/4'' NPT ext. thread, cable gland for signal line, circ. of Protec. two-tiered. Suitable for HART.
Surge protection in the IP67 screw-on module for measuring sensors, direct mounting with 3/4" NPT outer thread, cable gland for the signal line, two-stage protective circuit. HART-compatible. Can be used in safety-related circuits up to SIL 3.

Categories:

  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

LAST VIEWED

MORE INFO

Technical data

Notes
Notes on operationWhen the bridge is disconnected, the shield connection is indirectly connected to the housing or reference potential.

Product properties
Product typeSurge protection for MCR technology
Product familySURGETRAB
IEC test classificationC1
C2
C3
D1
TypeScrew-in module
Number of positions3
Surge protection fault messagenone
Wire pairs per module1
Data management status
Article revision12
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal voltage UN24 V DC

Connection data
Connection methodScrew connection
Screw threadM3
Tightening torque0.6 Nm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section rigid0.14 mm² ... 1.5 mm²
Conductor cross section AWG26 ... 16

Dimensions
Dimensional drawinguhcltedxcy.jpg
Width33.5 mm
Height33.5 mm
Depth148 mm

Material specifications
ColorSteel/stainless steel color
black (RAL 9005)
Housing materialZinc die-cast, surface bronzed and nickel-plated

Mechanical properties
Mechanical data
Open side panelNo

Protective circuit
Direction of actionLine-Line & Line-Earth Ground
Maximum continuous voltage UC40 V DC
28 V AC
Rated current450 mA (55 °C)
Operating effective current ICat UC≤ 10 µA
Residual current IPE≤ 2 µA
Nominal discharge current In(8/20) µs (line-line)10 kA
Nominal discharge current In(8/20) µs (line-ground)10 kA (per path)
Nominal discharge current In(8/20) µs (shield-ground)10 kA (optional)
Pulse discharge current Iimp(10/350) µs1 kA
Total discharge current Itotal(8/20) µs20 kA
Total discharge current Itotal(10/350) µs2 kA
Max. discharge current Imax(8/20) µs maximum (line-line)10 kA
Max. discharge current Imax(8/20) µs maximum (line-earth)10 kA (per path)
Discharge surge current Imax(8/20) µs maximum (shield-ground)10 kA
Nominal pulse current Ian (10/1000) µs (line-line)23 A
Nominal pulse current Ian (10/1000) µs (line-earth)100 A
Nominal pulse current Ian (10/1000) µs (shield-ground)100 A
Output voltage limitation at 1 kV/µs (line-line) spike≤ 55 V
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 450 V (Direct grounding)
Output voltage limitation at 1 kV/µs (shield-ground) spike≤ 600 V (optional)
Output voltage limitation at 1 kV/µs (line-line) static≤ 55 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 450 V (Direct grounding)
Residual voltage at In(conductor-conductor)≤ 55 V
Residual voltage with Ian (10/1000) µs (line-line)≤ 65 V
Voltage protection level Up(line-line)≤ 80 V (C2 - 10 kV / 5 kA)
Voltage protection level Up(line-earth)≤ 450 V (C2 - 10 kV / 5 kA)
Voltage protection level Up(shield-ground)≤ 600 V (C2 - 10 kV / 5 kA)
Voltage protection level Upstatic (line-line)≤ 50 V (C2 - 10 kV / 5 kA)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Response time tA (shield-ground)≤ 100 ns
Input attenuation aE, sym.typ. 0.5 dB (≤ 1.5 MHz / 50 Ω)
typ. 0.2 dB (≤ 300 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ω systemtyp. 6 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ω systemtyp. 2 MHz
Resistance per path2.2 Ω ±10 %
Surge protection fault messagenone
Max. required back-up fuse500 mA (T)
Impulse durability (line-line)C2 - 10 kV / 5 kA
D1 - 1 kA
Impulse durability (line-earth)C2 - 10 kV / 5 kA
D1 - 1 kA
Impulse durability (shield-ground)C2 - 10 kV/5 kA
D1 - 1 kA

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP67
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m (amsl)

Standards and regulations
Air clearances and creepage distances
Standards/regulationsIEC 60664-1 / VDE 0110-1
Standards/specificationsIEC 61643-21
Note2002

Mounting
Mounting typedirect screw connection

ETIM for 2882598 Earthing, lightning and surge protection (EC000943)

Feature nameNominal voltage DC (EF008799)
Feature value24 V

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.