PHOENIX CONTACT  VAL-MS 60 ST 2807573 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MS 60 ST 2807573 PHOENIX CONTACT Type 2 surge protection plug

Reference: VAL-MS 60 ST

Code: 2807573

Manufacturer: PHOENIX CONTACT

Description:

Type 2 surge protection plug
Plug-in type 2 surge protection with high-power varistor for VAL-MS base element, with thermal control, optical fault indication. Execution: 60 V AC

Categories:

  • Earthing, lightning and surge protection > Accessories/spare parts for surge protection power supply systems
  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 65,73 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey2807573
Packing unit10 pc
Catalog pagePage 58 (C-4-2017)
GTIN4017918075262
Weight per Piece (excluding packing)30.500 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN
Mode of protectionL-PEN
Mounting typeon base element
Colorjet black RAL 9005
Housing materialPA 6.6
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.10
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN60 V AC (TN)
60 V DC
-48 V DC (RRH)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC75 V AC
100 V DC
Residual current IPE≤ 0.45 mA
Standby power consumption PC≤ 35 mVA
Nominal discharge current In(8/20) µs15 kA
Maximum discharge current Imax(8/20) µs40 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 0.55 kV
Residual voltage Ures≤ 0.55 kV (at In)
≤ 0.425 kV (at 10 kA)
≤ 0.325 kV (at 5 kA)
≤ 0.275 kV (at 3 kA)
TOV behavior at UT100 V AC (5 s / withstand mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring125 A AC (gG)
50 A DC (gG)

Connection data

Connection methodpluggable

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-N)75 V AC
Maximum continuous operating voltage MCOV (L+) - (L-)100 V DC
Nom. voltage60 V AC
Nominal voltage60 V DC
Mode of protectionL-N
(L+) - (L-)
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)630 V
Measured limiting voltage MLV (L+) - (L-)810 V
Nominal discharge current In(L-N)10 kA
Nominal discharge current In(L+) - (L-)10 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications

DATASHEET - PDF

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.