PHOENIX CONTACT  VAL-CP-MOSO 60-3C-FM 2804416 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-CP-MOSO 60-3C-FM 2804416 PHOENIX CONTACT Type 2 surge arrester

Reference: VAL-CP-MOSO 60-3C-FM

Code: 2804416

Manufacturer: PHOENIX CONTACT

Description:

Type 2 surge arrester
Combination of type 2 surge protection and arrester pre-fuse, with arrester monitoring, in combination with status indication and remote indication contact. Version: 4-conductor system (L1, L2, L3, PEN), installation in 60 mm system technology (busbar system)

Categories:

  • Earthing, lightning and surge protection > Surge protection device for power supply systems
  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 498,46 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey2804416
Packing unit1 pc
Catalog pagePage 68 (C-4-2017)
GTIN4046356317832
Weight per Piece (excluding packing)1,200.000 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height220 mm
Width54 mm
Depth134 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 55 °C
Ambient temperature (storage/transport)-40 °C ... 75 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN-C
TT
Mode of protectionL-PEN
Mounting type60 mm system technology (power rail)
Colorblue-gray
jet black RAL 9005
Housing materialPBT
PA 6
PA 6.6
Degree of pollution2
Flammability rating according to UL 94V-0
TypeModule for 60 mm system technology
Number of positions3
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN240/415 V AC (TN-C)
240/415 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC350 V AC
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs25 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 2.5 kV
Residual voltage Ures≤ 2.1 kV (at In)
≤ 1.9 kV (at 10 kA)
≤ 1.8 kV (at 5 kA)
≤ 1.7 kV (at 3 kA)
TOV behavior at UT415 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiringnot required

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
125 V DC (200 mA DC)
Operating current5 mA AC ... 1 A AC
1 A DC (30 V DC)
Connection methodPluggable screw connection
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection namePEN conductor connection
Connection methodScrew connection
Screw threadM5
Tightening torque4.5 Nm
Stripping length16 mm
Conductor cross section flexible2.5 mm² ... 16 mm²
Conductor cross section solid2.5 mm² ... 25 mm²
Conductor cross section AWG12 ... 4
Connection namePhase conductor connection
Connection method60 mm power rail system

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

ETIM for 2804416 Earthing, lightning and surge protection (EC000941)

Feature nameSystem configuration DC (EF009926)
Feature valueNo
Feature nameSystem configuration IT (EF009927)
Feature valueNo
Feature nameSystem configuration TN (EF009928)
Feature valueNo
Feature nameSystem configuration TN-C (EF009929)
Feature valueYes
Feature nameSystem configuration TN-C-S (EF009933)
Feature valueNo
Feature nameSystem configuration TN-S (EF009930)
Feature valueNo
Feature nameSystem configuration TT (EF009931)
Feature valueNo
Feature nameSystem configuration other (EF009932)
Feature valueNo
Feature nameNominal discharge surge current (8/20) (EF004214)
Feature value20 kA
Feature nameMax. discharge surge current (8/20) (EF012274)
Feature value25 kA
Feature nameMax. continuous voltage AC (EF004198)
Feature value350 V
Feature nameVoltage protection level L-N (EF004236)
Feature value2.5 kV
Feature nameShort-circuit breaking capacity (Isccr) (EF012627)
Feature value25 kA
Feature nameIntegrated backup fuse (EF008797)
Feature valueYes
Feature nameLeakage-current free (EF016002)
Feature valueNo
Feature nameMax. conductor cross section solid (solid, stranded) (EF008827)
Feature value2.5 mm²
Feature nameMax. conductor cross section flexible (fine-strand) (EF008828)
Feature value16 mm²
Feature nameWith remote signalling contact (EF000422)
Feature valueYes
Feature nameSignalling at the device (EF004241)
Feature valueOptic
Feature nameCategory type 2 (EF004230)
Feature valueYes
Feature nameDegree of protection (IP) (EF005474)
Feature valueIP20

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.