PHOENIX CONTACT  VAL-MS 800/30 VF/FM 2805402 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MS 800/30 VF/FM 2805402 PHOENIX CONTACT Type 2 surge arrester

Reference: VAL-MS 800/30 VF/FM

Code: 2805402

Manufacturer: PHOENIX CONTACT

Description:

Type 2 surge arrester
Surge arrester composed of 2-channel base element with remote indication contact and varistor line-switched plug-in protections and gas-filled arc arrester.

Categories:

  • Earthing, lightning and surge protection > Surge protection device for power supply systems
  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 216,03 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey2805402
Packing unit1 pc
Catalog pagePage 56 (C-4-2017)
GTIN4046356498821
Weight per Piece (excluding packing)244.200 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height96.8 mm
Width35.6 mm
Depth65.7 mm (incl. DIN rail 7.5 mm)
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN
IT
Mode of protectionL-PE
L-PEN
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6
PBT
Degree of pollution2
Distance between live and grounded parts8 mm
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions2
Surge protection fault messageOptical, remote indicator contact

Additional descriptions

NoteFor use in all low-voltage systems between L-PEN.
Only for use in IT systems between L-PE if the bodies of the equipment in the low-voltage system are connected to the grounding system of the transformer station. (common grounding of the HV transformer station and the bodies of the LV consumer's installation. RE= RAaccording to IEC 60364-4-442/VDE 0100-442 Figure 44D/example a)

Protective circuit

Nominal voltage UN400/690 V AC (TN-C)
690 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC800 V AC
Rated load current IL80 A
Residual current IPE≤ 3 µA
Standby power consumption PC≤ 3 mVA
Nominal discharge current In(8/20) µs15 kA
Maximum discharge current Imax(8/20) µs30 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 5 kV
Residual voltage Ures≤ 3 kV (at In)
≤ 2.6 kV (at 10 kA)
≤ 2.4 kV (at 5 kA)
≤ 2.3 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 5 kV
TOV behavior at UT1550 V AC (5 s / withstand mode)
Response time tA≤ 100 ns
Max. backup fuse with V-type through wiring80 A (gG)
Max. backup fuse with branch wiring100 A (gG)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
30 V DC
Operating current5 mA AC ... 1.5 A AC
1 A DC
Connection methodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm (1,5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length16 mm
Conductor cross section flexible1.5 mm² ... 25 mm²
Conductor cross section solid1.5 mm² ... 35 mm²
Conductor cross section AWG15 ... 2
Connection methodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 16 mm²

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

ETIM for 2805402 Earthing, lightning and surge protection (EC000941)

Feature nameSystem configuration DC (EF009926)
Feature valueNo
Feature nameSystem configuration IT (EF009927)
Feature valueNo
Feature nameSystem configuration TN (EF009928)
Feature valueYes
Feature nameSystem configuration TN-C (EF009929)
Feature valueNo
Feature nameSystem configuration TN-C-S (EF009933)
Feature valueNo
Feature nameSystem configuration TN-S (EF009930)
Feature valueNo
Feature nameSystem configuration TT (EF009931)
Feature valueNo
Feature nameSystem configuration other (EF009932)
Feature valueNo
Feature nameNominal discharge surge current (8/20) (EF004214)
Feature value15 kA
Feature nameMax. discharge surge current (8/20) (EF012274)
Feature value30 kA
Feature nameMax. continuous voltage AC (EF004198)
Feature value800 V
Feature nameVoltage protection level L-N (EF004236)
Feature value5 kV
Feature nameMax. overcurrent protection device, parallel connection (fuse) (EF015962)
Feature value100 A
Feature nameMax. overcurrent protection device, series connection (fuse) (EF015963)
Feature value80 A
Feature nameShort-circuit breaking capacity (Isccr) (EF012627)
Feature value25 kA
Feature nameIntegrated backup fuse (EF008797)
Feature valueYes
Feature nameLeakage-current free (EF016002)
Feature valueNo
Feature nameMounting method (EF000003)
Feature valueDIN rail (top hat rail) 35 mm
Feature nameConstruction size (EF002566)
Feature valueOther
Feature nameMax. conductor cross section solid (solid, stranded) (EF008827)
Feature value1.5 mm²
Feature nameMax. conductor cross section flexible (fine-strand) (EF008828)
Feature value25 mm²
Feature nameWith remote signalling contact (EF000422)
Feature valueYes
Feature nameSignalling at the device (EF004241)
Feature valueOptic
Feature nameCategory type 2 (EF004230)
Feature valueYes
Feature nameDegree of protection (IP) (EF005474)
Feature valueIP20

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.