PHOENIX CONTACT  NEF 1-3 2794110 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

NEF 1- 3 2794110 PHOENIX CONTACT EMC filter

Reference: NEF 1-3

Code: 2794110

Manufacturer: PHOENIX CONTACT

Description:

EMC filter
Pest filter with universal foot for mounting on NS 32 and NS 35/7.5, nominal current: 3 A

Categories:

  • Earthing, lightning and surge protection > Surge protection device for terminal equipment
  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

MORE INFO

Key Commercial Data

Orderkey2794110
Packing unit10 pc
Catalog pagePage 187 (C-4-2017)
GTIN4017918072803
Weight per Piece (excluding packing)85.120 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height79.4 mm
Width25 mm
Depth84.15 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 100 °C (HMF)
Degree of protectionIP20

General

Housing materialPA
Flammability rating according to UL 94V-2
Colorblack
Standards for cearances and creepage distancesIEC 60664-1
VDE 0110-1
Mounting typeDIN rail: 35 mm
TypeDIN rail module, one-piece
Number of positions2
Direction of action1L-N & N-PE

Protective circuit

Maximum continuous voltage UC264 V AC (L-N)
264 V AC (L-PE)
Nominal frequency fN50 Hz (60 Hz)
Rated current3 A (40 °C)
Operating effective current ICat UC≤ 0.25 mA
Residual current IPE≤ 0.5 mA
Input attenuation aE, sym.> 55 dB (50 Ω / 1 MHz)
Input attenuation aE, asym.> 35 dB (50 Ω / 1 MHz)
Capacity2x 100 nF (X2)
2x 2.2 nF (Y2)
Inductivity in series2x 2.7 mH (with current compensation)
Max. required back-up fuse3 A (gL)

Connection data

Connection methodScrew connection
Connection method INScrew terminal blocks
Connection method OUTScrew terminal blocks
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/specificationsIEC 60939-2
EN 60939-2

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

DATASHEET - PDF

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.