PHOENIX CONTACT  DT-UFB-V24/S-9-SB 2803069 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

DT-UFB-V24/S-9-SB 2803069 PHOENIX CONTACT Surge protection device

Reference: DT-UFB-V24/S-9-SB

Code: 2803069

Manufacturer: PHOENIX CONTACT

Description:

Surge protection device
Adapter with surge protection for V.24 interface. Connection: Male-female D-SUB-9, for in-line mounting

Categories:

  • Earthing, lightning and surge protection > Surge protection device for data networks/MCR-technology
  • PHOENIX CONTACT > Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX CONTACT

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 199,53 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Key Commercial Data

Orderkey2803069
Packing unit1 pc
Catalog pagePage 144 (C-4-2017)
GTIN4046356312974
Weight per Piece (excluding packing)300.550 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height102 mm
Width25 mm
Depth63.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialZinc die-cast
Colorsilver/black
Standards for cearances and creepage distancesIEC 60664-1
VDE 0110-1
Mounting typeConnection-specific attachment plug and DIN rail, 35 mm
TypeAttachment plug for DIN rail mounting
Number of positions9
Direction of actionLine-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground

Protective circuit

IEC test classificationB2
C1
C2
C3
VDE requirement classB2
C1
C2
C3
Maximum continuous voltage UC15 V DC
10 V AC
Rated current≤ 1 A (25 °C)
Operating effective current ICat UC≤ 5 µA (per wire)
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (line-line)≤ 250 A
Nominal discharge current In(8/20) µs (line-earth)≤ 250 A
Nominal discharge current In(8/20) µs (core-signal ground)≤ 250 A
Nominal discharge current In(8/20) µs (signalground-earth)≤ 5 kA
Total discharge current Itotal(8/20) µs5 kA
Nominal pulse current Ian (10/1000) µs (line-line)50 A
Nominal pulse current Ian (10/1000) µs (line-earth)50 A
Nominal pulse current Ian (10/1000) µs (line-signalground)50 A
Nominal pulse current Ian (10/700) µs (line-line)50 A
Nominal pulse current Ian (10/700) µs (line-earth)50 A
Nominal pulse current Ian (10/700) µs (line-signalground)50 A
Output voltage limitation at 1 kV/µs (line-line) static≤ 50 V
Output voltage limitation at 1 kV/µs (line-signalground) static≤ 30 V
Residual voltage at In(line-line)≤ 55 V
Residual voltage at In(line-signalground)≤ 30 V
Voltage protection level Up(line-line)≤ 55 V (C1 - 250 A)
≤ 55 V (B2 - 25 A)
Voltage protection level Up(line-earth)≤ 450 V (C1 - 250 A)
≤ 400 V (B2 - 25 A)
Voltage protection level Up(line-signalground)≤ 30 V (C1 - 250 A)
≤ 30 V (B2 - 25 A)
Response time tA(line-line)≤ 1 ns
Response time tA (line-signalground)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Response time tA (shield-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 700 kHz / 100 Ω)
typ. 0.3 dB (≤ 700 kHz / 150 Ω)
Input attenuation aE, asym.typ. 0.3 dB (≤ 400 kHz / 100 Ω)
typ. 0.3 dB (≤ 400 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ohm systemtyp. 2.5 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 2.5 MHz
Cut-off frequency fg (3 dB), asym. (GND) in 100 Ohm systemtyp. 1.3 MHz
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm systemtyp. 1.3 MHz
Capacity (line-line)typ. 1 nF (f=1 MHz / VR= 0 V)
Capacity (line-signalground)typ. 2 nF (f=1 MHz / VR= 0 V)
Surge protection fault messagenone
Impulse durability (line-line)B2 - 1 kV / 25 A
C1 - 500 V / 250 A
Impulse durability (line-signalground)B2 - 1 kV/25 A
C1 - 500 V/250 A
Impulse durability (signalground-earth)B2 - 4 kV / 100 A
C1 - 100 V / 500 A
C2 - 10 kV/5 kA
Alternating current carrying capacity (signalground-earth)5 A - 1 s

Connection data

Connection methodD-SUB-9
Connection method IND-SUB-9 plug
Connection method OUTD-SUB-9 socket

Connection, equipotential bonding

Connection methodCable connection/DIN rail

Standards and Regulations

Standards/regulationsIEC 61643-21
Standards/specificationsDIN EN 61643-21 2002
IEC 61643-21 2000

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.