OMRON EJ1C-EDUA-NFLK EJ1C1000H EJ1CEDUANFLK - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

EJ1C-EDUA-NFLK EJ1C1000H EJ1CEDUANFLK OMRON EJ1 Header Alim, Coms, Alarm

Reference: EJ1C-EDUA-NFLK

Code: EJ1C1000H

Catalog Number: EJ1CEDUANFLK

Manufacturer: OMRON

Description:

EJ1 Header Alim, Coms, Alarm
CelciuXº In-panel temperature controller end unit, connects up to 16 x basic & high function units, 24 VDC supply, 1 x RS-485 port (115kbps, CompoWay/
CelciuXº In-panel temperature controller end unit, connects up to 16 x basic & high function units, 24 VDC supply, 1 x RS-485 port (115kbps, CompoWay/

Categories:

  • PLC's > PLC system power supply
  • OMRON > Temperature Control Panel > EJ1

Brand new product in its original packaging covered by the warranties and certifications provided by OMRON

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 234,39 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-3 days.

  • These delivery times are an estimate any may vary when the item order has been processed.

MORE INFO

Features

CelciuXº - Multi-Loop temperature control - Control and Connectivity

CelciuXº is designed to offer easy program-less communication with Omron and third-party PLCs and HMI. Above all, CelciuXº (EJ1) incorporates all âsimple to useâ clever temperature control technology, like 2-PID, disturbance control and various ways of tuning.

  • Interfaces to a wide range of industrial networks
  • Reduced engineering due to Programm-less communications, Smart Active Parts and Function Block Libraries
  • Available with screw terminals and screw-less clamp terminals
  • One unit handling various types of input, such as Pt, Thermocouple, mA, and V input

Applications

The perfect solution for multi-loop control

Reliability, compactness and uncompromising control performance make the CelciuX° the perfect choice for basic multi-loop control.

Multi-loop machine control with hmi

Control, overview and>

Ordering information

Type Control points Control outputs Auxiliary outputs Other functions Terminal Order code
Basic unit 2 2 voltage (pulse) 2 transistor (NPN)
2
For heating/cooling control applications, the auxiliary outputs on the 2-point models are used for cooling control.
On the 4-point models, heating/cooling control can be performed for two input points only.
2 CT input
2
When usingthe heater burnout alarm, purchase a Current Transformer (E54-CT1or E54-CT3) separately.
+ 2 event input
M3 screws EJ1N-TC2A-QNHB
Basic unit 2 2 voltage (pulse) 2 transistor (NPN)
2
For heating/cooling control applications, the auxiliary outputs on the 2-point models are used for cooling control.
On the 4-point models, heating/cooling control can be performed for two input points only.
2 CT input
2
When usingthe heater burnout alarm, purchase a Current Transformer (E54-CT1or E54-CT3) separately.
+2 event input
Screw-less clamp EJ1N-TC2B-QNHB
Basic unit 2 2 current 2 transistor (NPN)
2
For heating/cooling control applications, the auxiliary outputs on the 2-point models are used for cooling control.
On the 4-point models, heating/cooling control can be performed for two input points only.
2 event input M3 screws EJ1N-TC2A-CNB
Basic unit 2 2 current 2 transistor (NPN)
2
For heating/cooling control applications, the auxiliary outputs on the 2-point models are used for cooling control.
On the 4-point models, heating/cooling control can be performed for two input points only.
2 event input Screw-less clamp EJ1N-TC2B-CNB
Basic unit 4 4 voltage (pulse) – – M3 screws EJ1N-TC4A-QQ
Basic unit 4 4 voltage (pulse) – – Screw-less clamp EJ1N-TC4B-QQ
High function unit – – 4 transistor (NPN) 4 event input M3 screws EJ1N-HFUA-NFLK
High function unit – – 4 transistor (NPN) 4 event input Screw-less clamp EJ1N-HFUB-NFLK
DeviceNet unit – – – – Screw connector EJ1N-HFUB-DRT
Ethernet unit
2
This unit mounts to the left of the CelciuX° (EJ1) configuration and enables PROFINET or Modbus/TCP network connection.
Combine the HFU-ETN with an EDU_-NFLK end unit to use with other devices supporting Modbus-RTU like E5_N temperature controllers and MX2 Inverters.
– – – – 3 x RJ45 EJ1N-HFU-ETN
End unit
2
An End unitis always required for connection to a Basic unit or an HFU. AnHFU cannot operate without a Basic unit.
– – 2 transistor (NPN) – M3 screws EJ1C-EDUA-NFLK
End unit
2
An End unitis always required for connection to a Basic unit or an HFU. AnHFU cannot operate without a Basic unit.
– – 2 transistor (NPN) – Removable Connector EJ1C-EDUC-NFLK

Accessories

Currenttransformer

Diameter Order code
5.8 dia. E54-CT1
12.0 dia. E54-CT3

Communications and cables

Description Order code
G3ZA connecting cable 5 meter EJ1C-CBLA050
USB programming cable E58-CIFQ1
PC based configuration and tuning softwareCX-Thermo EST2-2C-MV4
PROFIBUS Gateway PRT1-SCU11

Specifications

Item Type EJ1_-TC2 EJ1_-TC4
Power supplyvoltage 24 VDC
Operatingvoltage range 85% to 110% of rated voltage
Power consumption 4 W max. (at maximum load) 5 W max. (at maximum load)
Input (seenote)
2
Inputs are fully multi-input. Therefore, platinum resistancethermometer, thermocouple, infrared thermosensor, and analog inputcan be selected.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
ES1B Infrared Thermosensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C.
Analog input: 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 10 VPlatinumresistance thermometer: Pt100, JPt100
Input impedance Current input: 150Ω max., voltageinput: 1 MΩ min.
Controloutputs Voltage output Output voltage: 12 VDC ±15%, max.load current: 21 mA (PNP models with short-circuit protection circuit)
Transistor output Max. operating voltage: 30 V, max.load current: 100 mA –
Current output Current output range: 4 to 20 mA or 0 to 20mA DCLoad: 500 Ω max. (including transfer output)(Resolution: Approx:2,800 for 4 to 20 mA DC, approx. 3,500 for 0 to 20 mA DC) –
Event inputs Input points 2 –
Contact input ON: 1 kΩ max., OFF. 100 kΩ min. –
Non-contact input ON: Residual voltage: 1.5 V max.,OFF: Leakage current: 0.1 mA max. –
Outflow current: approx. 4 mA per point –
Number ofinput and control points Input points: 2, control points: 2 Input points: 4, control points: 4
Setting method Via communications
Control method ON/OFF control or 2-PID (withautotuning, selftuning, Heat & Cool autotuning and non-linearcool output selection)
Other functions Two-point input shift, digital input filter, remote SP, SP ramp, manual manipulated variable,
manipulated variable limiter, interference overshoot adjustment, loop burnout alarm, RUN/STOP, banks, I/O allocations, etc.
Alarm output 2 points via End unit
Communication RS-485, PROFIBUS, Modbus, DeviceNet RS-485, PROFIBUS, Modbus, DeviceNet
Size in mm(W×H×D) 31×96×109
Weight 180 g
Ambient temperaturerange Operating –10 to 55°C, Storage–25 to 65°C (with no icing or condensation)
Ambient humidityrange Operating 25% to 85% (with nocondensation)

Dimensions

Item Size in mm (H×W×D)
EJ1N-HFU_-NFL_ 95.4×31.0×104.9/109.0
EJ1N-HFUB-DRT 90.9×31.0×82.2
EJ1C-EDU 95.4×15.7×76.2/79.7

ETIM for 225933 PLC's (EC000599)

Feature nameType of voltage (input voltage) (EF003033)
Feature valueDC
Feature nameType of output voltage (EF008222)
Feature valueDC
Feature nameRedundancy (EF003156)
Feature valueNo
Feature nameSuitable for safety functions (EF001597)
Feature valueNo
Feature nameWidth (EF000008)
Feature value15.7 mm
Feature nameHeight (EF000040)
Feature value95.4 mm
Feature nameDepth (EF000049)
Feature value79.7 mm
Feature nameOutput voltage DC (EF007001)
Feature value24 V
Feature nameInput voltage DC (EF007120)
Feature value20.4 V

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.