EATON - MOELLER P1-32/SE1/SVB-SW 197357 Y7-197357 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

P1-32/SE1/SVB-SW 197357 EATON ELECTRIC General Switch. 32A. surface mounting. 3p. Stop function.

Reference: P1-32/SE1/SVB-SW

Code: 197357

Catalog Number: Y7-197357

Manufacturer: EATON - MOELLER

Description:

General Switch. 32A. surface mounting. 3p. Stop function.
Main switch, P1, Rated uninterrupted current (Iu): 32 A, Functions: STOP function, Interlockable, Fitted with: Black rotary handle and locking ring, Mounting method: Surface mounting, Number of poles: Three-pole, Locking facility: Lockable in the 0 (Off) position, Degree of Protection: NEMA 12

Categories:

  • Low-voltage industrial components > Switch disconnector
  • EATON - MOELLER > Disconnectors and Cam Switches

Brand new product in its original packaging covered by the warranties and certifications provided by EATON - MOELLER

  • More Info
  • ETIM
  • Reviews
Guarantee, repair and return.

Unit Price: 143,06 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

General specifications

Product Name
Eaton Moeller® series P1 Main switch
Catalog Number
197357
Model Code
P1-32/SE1/SVB-SW
EAN
4015080896876
Product Length/Depth
200 mm
Product Height
135 mm
Product Width
150 mm
Product Weight
1.65 kg
Certifications
IEC/EN 60204
IEC/EN 60947
VDE 0660
IEC/EN 60947-3

Features & Functions

Features
Version as maintenance-/service switch
Version as main switch
Fitted with:
Black rotary handle and locking ring
Functions
Interlockable
STOP function
Locking facility
Lockable in the 0 (Off) position
Number of poles
Three-pole

General

Accessories
Auxiliary contact or neutral conductor fitted by user.
Degree of protection
NEMA 12
Degree of protection (front side)
IP65
Lifespan, mechanical
300,000 Operations
Mounting method
Surface mounting
Mounting position
As required
Operating frequency
1200 Operations/h
Overvoltage category
III
Pollution degree
3
Product Category
Main switch
Rated impulse withstand voltage (Uimp)
6000 V AC
Safe isolation
440 V AC, Between the contacts, According to EN 61140
Safety parameter (EN ISO 13849-1)
B10d values as per EN ISO 13849-1, table C.1
Shock resistance
15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Suitable for
Ground mounting
Switching angle
90 °

Climatic environmental conditions

Ambient operating temperature (enclosed) - min
-25 °C
Ambient operating temperature (enclosed) - max
40 °C

Terminal capacities

Terminal capacity
2 x (1 - 4) mm², flexible with ferrules to DIN 46228
1 x (1.5 - 6) mm², solid or stranded
1 x (1 - 4) mm², flexible with ferrules to DIN 46228
2 x (1.5 - 6) mm², solid or stranded
Screw size
M4, Terminal screw
Tightening torque
14 Nm, Screw terminals
1.6 Nm, Screw terminals

Electrical rating

Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3)
260 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)
300 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)
290 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)
250 A
Rated operational current (Ie) at AC-21, 440 V
32 A
Rated operational current (Ie) at AC-23A, 230 V
32 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V
32 A
Rated operational current (Ie) at AC-23A, 500 V
30 A
Rated operational current (Ie) at AC-23A, 690 V
19.8 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V
26.4 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
26.4 A
Rated operational current (Ie) at AC-3, 500 V
23.4 A
Rated operational current (Ie) at AC-3, 660 V, 690 V
14.7 A
Rated operational current (Ie) at DC-1, load-break switches l/r = 1 ms
32 A
Rated operational current (Ie) at DC-23A, 120 V
12 A
Rated operational current (Ie) at DC-23A, 24 V
25 A
Rated operational current (Ie) at DC-23A, 48 V
25 A
Rated operational current (Ie) at DC-23A, 60 V
25 A
Rated operational power at AC-23A, 220/230 V, 50 Hz
7.5 kW
Rated operational power at AC-23A, 400 V, 50 Hz
15 kW
Rated operational power at AC-23A, 500 V, 50 Hz
18.5 kW
Rated operational power at AC-23A, 690 V, 50 Hz
15 kW
Rated operational power at AC-3, 380/400 V, 50 Hz
13 kW
Rated operational power at AC-3, 415 V, 50 Hz
13 kW
Rated operational power at AC-3, 690 V, 50 Hz
15 kW
Rated operational voltage (Ue) at AC - max
690 V
Rated uninterrupted current (Iu)
32 A
Uninterrupted current
Rated uninterrupted current Iu is specified for max. cross-section.
Uninterrupted current
Rated uninterrupted current Iu is specified for max. cross-section.

Short-circuit rating

Rated conditional short-circuit current (Iq)
80 kA
Rated short-time withstand current (Icw)
0.64 kA
640 A, Contacts, 1 second
Short-circuit protection rating
50 A gG/gL, Fuse, Contacts

Switching capacity

Number of contacts in series at DC-23A, 24 V
1
Number of contacts in series at DC-23A, 48 V
2
Number of contacts in series at DC-23A, 60 V
2
Number of contacts in series at DC-23A, 120 V
3
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3)
320 A
Voltage per contact pair in series
60 V
Load rating
1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor)
2 x Iₑ (with intermittent operation class 12, 25 % duty factor)
1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor)

Contacts

Control circuit reliability
1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0

Actuator

Actuator color
Black
Actuator type
Door coupling rotary drive

Design verification

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
UV resistance only in connection with protective shield.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

ETIM for 197357 Low-voltage industrial controls and switchgear (EC000216)

Feature nameVersion as main switch (EF006981)
Feature valueYes
Feature nameVersion as maintenance-/service switch (EF006986)
Feature valueYes
Feature nameVersion as safety switch (EF006985)
Feature valueNo
Feature nameVersion as emergency stop installation (EF006959)
Feature valueNo
Feature nameVersion as reversing switch (EF009408)
Feature valueNo
Feature nameNumber of switches (EF005586)
Feature value1
Feature nameMax. rated operation voltage Ue AC (EF007355)
Feature value690 V
Feature nameRated operating voltage (EF001435)
Feature value690 V
Feature nameRated permanent current Iu (EF001389)
Feature value32 A
Feature nameRated permanent current at AC-23, 400 V (EF011777)
Feature value32 A
Feature nameRated permanent current at AC-21, 400 V (EF009165)
Feature value32 A
Feature nameRated operation power at AC-3, 400 V (EF001364)
Feature value13 kW
Feature nameRated short-time withstand current lcw (EF007050)
Feature value0.64 kA
Feature nameRated operation power at AC-23, 400 V (EF007027)
Feature value15 kW
Feature nameSwitching power at 400 V (EF009166)
Feature value15 kW
Feature nameConditioned rated short-circuit current Iq (EF001444)
Feature value80 kA
Feature nameNumber of poles (EF001391)
Feature value3
Feature nameNumber of auxiliary contacts as normally closed contact (EF001377)
Feature value0
Feature nameNumber of auxiliary contacts as normally open contact (EF001376)
Feature value0
Feature nameNumber of auxiliary contacts as change-over contact (EF003531)
Feature value0
Feature nameMotor drive optional (EF007386)
Feature valueNo
Feature nameMotor drive integrated (EF006697)
Feature valueNo
Feature nameVoltage release optional (EF007491)
Feature valueNo
Feature nameDevice construction (EF008240)
Feature valueComplete device in housing
Feature nameSuitable for front mounting 4-hole (EF007247)
Feature valueNo
Feature nameSuitable for front mounting centre (EF007248)
Feature valueNo
Feature nameSuitable for distribution board installation (EF007262)
Feature valueNo
Feature nameSuitable for intermediate mounting (EF007264)
Feature valueNo
Feature nameColour control element (EF007167)
Feature valueBlack
Feature nameType of control element (EF006976)
Feature valueDoor coupling rotary drive
Feature nameInterlockable (EF006281)
Feature valueYes
Feature nameType of electrical connection of main circuit (EF006819)
Feature valueScrew connection
Feature nameWith pre-assembled cabling (EF016444)
Feature valueNo
Feature nameDegree of protection (IP), front side (EF003118)
Feature valueIP65
Feature nameDegree of protection (NEMA) (EF011959)
Feature value12
Feature nameWidth (EF000008)
Feature value150 mm
Feature nameHeight (EF000040)
Feature value135 mm
Feature nameDepth (EF000049)
Feature value200 mm

DATASHEET - PDF

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.