BT-1S-230AC/A 2803409 PHOENIX CONTACT Type 3 surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

BT-1S-230AC/A 2803409 PHOENIX CONTACT Type 3 surge protection device

BT-1S-230AC/A

2803409

PHOENIX_CONTACT

Type 3 surge protection device

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $96.59
Unit price: $96.59

Quantity Price
1+$96.59
2+$88.71
3+$81.14
4+$76.86
5+$74.05
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2803409
Packing unit10 pc
Catalog pagePage 73 (C-4-2017)
GTIN4046356350976
Weight per Piece (excluding packing)27.350 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height43 mm
Width22.5 mm
Depth26.2 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-30 °C ... 75 °C
Ambient temperature (storage/transport)-30 °C ... 75 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %

General

EN typeT3
IEC power supply systemTN-S
TT
IT with N conductor
Number of portsOne
Mode of protectionL-N
L-PE
N-PE
Mounting typeScrew mounting
Colorjet black RAL 9005
Housing materialPA 6.6
Degree of pollution2
Distance between live and grounded parts3 mm
Flammability rating according to UL 94V-0
TypeInstallation module
Number of positions2
Surge protection fault messageAcoustic

Protective circuit

Nominal voltage UN230/400 V AC (TN-S)
230/400 V AC (TT - only in use with RCD)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC(L-N)275 V AC
Maximum continuous operating voltage UC(L-PE)440 V AC
Maximum continuous operating voltage UC(N-PE)440 V AC
Rated load current IL16 A (30 °C)
Residual current IPE≤ 3 µA
Nominal discharge current In(8/20) µs3 kA
Standby power consumption PC≤ 400 mVA
Reference test voltage UREF255 V AC
Max. discharge current Imax(8/20) µs8 kA
Combination wave UOC6 kV
Voltage protection level Up(L-N)≤ 1.3 kV
Voltage protection level Up(L-PE)≤ 1.5 kV
Voltage protection level Up(N-PE)≤ 1.5 kV
TOV behavior at UT(L-N)335 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
TOV behavior at UT(L-PE)440 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
1455 V AC (200 ms / safe failure mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / safe failure mode)
Response time tA(L-N)≤ 25 ns
Response time tA(L-PE)≤ 100 ns
Max. required back-up fuse16 A (MCB B)
Short-circuit current rating ISCCR1 kA AC
Max. backup fuse with branch wiring16 A (MCB B)
Maximum backup fuse for through wiring16 A (MCB B)

Connection data

Connection methodSpring-cage connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Stripping length10 mm

Standards and Regulations

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.