VAL-CP-350-ST 2859602 PHOENIX CONTACT Replacement plug for VAL-CP surge arrester with high-capacity varistor.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-CP-350-ST 2859602 PHOENIX CONTACT Replacement plug for VAL-CP surge arrester with high-capacity varistor..

VAL-CP-350-ST

2859602

PHOENIX_CONTACT

10

Available

Ship on today

Replacement plug for VAL-CP surge arrester with high-capacity varistor free of leakage current.

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
10+$50.04
20+$48.40
30+$47.64
40+$47.61
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Height46.4 mm
Width11.7 mm
Depth56.4 mm
Horizontal pitch0.6 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012
IEC test classificationII
T2
EN typeT2
IEC power supply systemTN
TT
SPD designVoltage-limiting type
Mode of protectionL-PEN
L-N
Mounting typeOn base element
Colorgray/blue
Housing materialPBT-FR
Pollution degree2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions1
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN240 V AC (TN)
240 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC350 V AC
Nominal discharge current In (8/20) µs20 kA
Maximum discharge current Imax (8/20) µs40 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures≤ 1.5 kV (at In)
≤ 1.3 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 4 kA)
≤ 1 kV (at 2 kA)
TOV behavior at UT415 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring315 A AC (gG)

Connection data

Connection methodVALVETRAB plug-in system

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-N)350 V AC
Nom. voltage277 V AC
Mode of protectionL-N
Power distribution system1
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)2000 V
Nominal discharge current In (L-N)20 kA

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2859602-VAL-CP-350-ST English 118 Kbytes PHOENIX CONTACT-2859602-VAL-CP-350-ST

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.