TTC-6-2-24DC-UT 2906800 PHOENIX CONTACT Surge protection for resistance-dependent measuring signals. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

TTC-6-2-24DC-UT 2906800 PHOENIX CONTACT Surge protection for resistance-dependent measuring signals.

TTC-6-2-24DC-UT

2906800

PHOENIX_CONTACT

Surge protection for resistance-dependent measuring signals.

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $112.42
Unit price: $112.42

Quantity Price
1+$112.42
2+$99.99
3+$92.01
4+$87.49
5+$86.20
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Key Commercial Data

Orderkey2906800
Packing unit1 pc
Catalog pagePage 143 (C-4-2019)
GTIN4055626135557
Weight per Piece (excluding packing)40.000 g
Custom tariff number85363010
Country of originDE (Germany)

Drawings



Diagram

Diagram

Dimensional drawing

Dimensional drawing



Pictogram

Pictogram

Circuit diagram

Circuit diagram



Back to top

Dimensions

Height105.8 mm
Width6.2 mm +0.1 mm
Depth69.5 mm (incl. DIN rail 7.5 mm)
Back to top

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 %
Altitude≤ 4000 m (amsl (above mean sea level))
Degree of protectionIP20
Back to top

General

Housing materialPBT
Flammability rating according to UL 94V-0
Colortraffic grey A RAL 7042
Mounting typeDIN rail: TH 35 - 7.5 mm
TypeDIN rail module, one-piece
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Back to top

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC30 V DC
21 V AC
Rated current450 mA (80 °C)
Operating effective current ICat UC≤ 5 µA
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (line-line)0.5 kA
Nominal discharge current In(8/20) µs (line-earth)5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA
Total discharge current Itotal(8/20) µs10 kA
Voltage protection level Up(line-line)≤ 60 V (C1 - 1 kV/500 A)
≤ 45 V (C3 - 25 A)
≤ 50 V (C3 - 100 A)
Voltage protection level Up(line-earth)≤ 650 V (C1 - 1 kV/500 A)
≤ 1.1 kV (C2 - 10 kV / 5 kA)
≤ 600 V (C3 - 25 A)
≤ 700 V (C3 - 100 A)
Voltage protection level Upstatic (line-earth)≤ 1.1 kV (C2 - 10 kV / 5 kA)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 300 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 965 kHz
Capacity (line-earth)typ. 2.2 nF
Resistance per path≤ 100 mΩ
Max. required back-up fuse500 mA (FF)
Impulse durability (line-line)C1 - 1 kV / 500 A
C3 - 100 A
Impulse durability (line-earth)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-earth)≤ 1 s
Back to top

Additional technical data

Max. total discharge current Itotal max(8/20) µs20 kA (1x)
Back to top

Connection data

Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Back to top

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21 2001 + A1:2009 + A2:2013
Back to top

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 4.027140201
eCl@ss 4.127130801
eCl@ss 5.027130801
eCl@ss 5.127130801
eCl@ss 6.027130800
eCl@ss 7.027130807
eCl@ss 8.027130807
eCl@ss 9.027130807
Back to top

ETIM

ETIM 2.0EC000943
ETIM 3.0EC000943
ETIM 4.0EC000943
ETIM 5.0EC000943
ETIM 6.0EC000943
ETIM 7.0EC000943
Back to top

UNSPSC

UNSPSC 6.0130212010
UNSPSC 7.090139121610
UNSPSC 1139121610
UNSPSC 12.0139121610
UNSPSC 13.239121620
UNSPSC 18.039121620
UNSPSC 19.039121620
UNSPSC 20.039121620
UNSPSC 21.039121620
Back to top

Datasheet - PDF

Title: Size: Type:
PDF CATALOG PHOENIX PROTECTION EN.pdf 27 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.