UTWE 6-2/D19 3069418 PHOENIX CONTACT Test terminal strip View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

UTWE 6-2/D19 3069418 PHOENIX CONTACT Test terminal strip

UTWE 6-2/D19

3069418

PHOENIX_CONTACT

Test terminal strip

More details


Terminal blocks > (Knife) disconnect terminal block

Enclosures connectivity

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $576.41
Unit price: $576.41

Quantity Price
1+$576.41
2+$544.58
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey3069418
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 608 (C-1-2017)
GTIN4046356943130
Weight per Piece (excluding packing)599.700 g
Custom tariff number85369010
Country of originPL (Poland)

General

Number of positions19
Number of levels1
Number of connections38
Potentials19
Nominal cross section6 mm²
Colorgray
Insulating materialPA
Flammability rating according to UL 94V0
Rated surge voltage4 kV
Test surge voltage5 kV
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition1.31 W
Maximum load current30 A (with 10 mm² conductor cross section)
Current Ith24 A
Nominal voltage UN400 V AC/DC
Open side panelNo
Terminal block mounting0.8 Nm ... 1 Nm
Result of surge voltage testTest passed
Surge voltage test setpoint4.8 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)Test passed
Result of bending testTest passed
Bending test rotation speed10 rpm
Bending test turns135
Bending test conductor cross section/weight0.2 mm² / 0.2 kg
6 mm2/ 1.4 kg
10 mm² / 2 kg
Tensile test resultTest passed
Conductor cross section tensile test0.2 mm²
Tractive force setpoint10 N
Conductor cross section tensile test6 mm²
Tractive force setpoint80 N
Conductor cross section tensile test10 mm²
Tractive force setpoint90 N
Result of tight fit on supportTest passed
Setpoint5 N
Result of voltage-drop testTest passed
Requirements, voltage drop≤ 4.8 mV
Result of temperature-rise testTest passed
Short circuit stability resultTest passed
Conductor cross section short circuit testing4 mm²
Short-time current300 A
Conductor cross section short circuit testing4 mm²
Short-time current500 A
Result of thermal testTest passed
Ageing test for screwless modular terminal block temperature cycles192
Proof of thermal characteristics (needle flame) effective duration30 s
Result of aging testTest passed
Oscillation, broadband noise test resultTest passed
Test specification, oscillation, broadband noiseDIN EN 50155 (VDE 0115-200):2008-03
Test spectrumService life test category 2, bogie-mounted
Test frequencyf1= 5 Hz to f2= 250 Hz
ASD level6.12 (m/s2)2/Hz
Acceleration3.12 g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
Shock test resultTest passed
Test specification, shock testDIN EN 50155 (VDE 0115-200):2008-03
Shock formHalf-sine
Acceleration30g
Shock duration18 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))125 °C
Static insulating material application in cold-60 °C
Behavior in fire for rail vehicles (DIN 5510-2)Test passed
Flame test method (DIN EN 60695-11-10)V0
Oxygen index (DIN EN ISO 4589-2)>32 %
NF F16-101, NF F10-102 Class I2
NF F16-101, NF F10-102 Class F2
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Calorimetric heat release NFPA 130 (ASTM E 1354)27,5 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Dimensions

Width188.6 mm
Length100 mm
Height56.5 mm
Plate thickness1 mm ... 4 mm
Pitch8.2 mm

Connection data

Connection methodScrew connection
Screw threadM4
Stripping length12 mm
Tightening torque, min1.5 Nm
Tightening torque max1.8 Nm
Connection in acc. with standardIEC 60947-7-1
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.10 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.8
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.10 mm²
Min. AWG conductor cross section, flexible24
Max. AWG conductor cross section, flexible8
Conductor cross section flexible, with ferrule without plastic sleeve min.0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.6 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.6 mm²
2 conductors with same cross section, solid min.0.2 mm²
2 conductors with same cross section, solid max.2.5 mm²
2 conductors with same cross section, stranded min.0.2 mm²
2 conductors with same cross section, stranded max.2.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min.0.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max.2.5 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min.0.25 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max.1.5 mm²
Internal cylindrical gageA5

Mounting

Mounting typeWall mounting
Plate thickness1 mm ... 4 mm
Min. tightening torque of the mounting screw:0.8 Nm
Max. tightening torque of the mounting screw:1 Nm

Standards and Regulations

Connection in acc. with standardIEC 60947-7-1
Flammability rating according to UL 94V0
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.