ANUNCIAR
MACX MCR-T-UI-UP 2811394 PHOENIX CONTACT Freely programmable temperature transducer with analog output and 1.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MACX MCR-T-UI-UP 2811394 PHOENIX CONTACT Freely programmable temperature transducer with analog output and 1..

MACX MCR-T-UI-UP

2811394

PHOENIX_CONTACT

Freely programmable temperature transducer with analog output and 1 limit value relay, standard configuration, resistance thermometer in 2-, 3-, or 4-wire technology, thermocouples, galvanic isolation, wide-range power supply, screw connection, SIL

Freely programmable temperature converter with analog output and 1 limit value relay, standard configuration, heat resistances in 2, 3 or 4 conductor technology, thermocouples, galvanic separation, wide power range, screw connection, SIL, PL.

More details


Sensors > Temperature transformer

INTERFACE Components (IF)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $630.96
Unit price: $630.96
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width17.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 2000 m
Permissible humidity (operation)typ. 5 % ... 95 % (non-condensing)
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Input data

Sensor types (RTD) that can be usedPt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC)B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range-250 °C ... 2500 °C (Range depending on the sensor type)
Input signal range0 Ω ... 50 kΩ
Potentiometer resistance range0 Ω ... 50 kΩ
Input signal range-1000 mV ... 1000 mV

Output data

Max. voltage output signal± 11 V
Current output signal0 mA ... 20 mA ±10 V (in the case of SIL; further free configuration without SIL)
Max. current output signal22 mA
Load/output load voltage output≥ 10 kΩ
Load/output load current output≤ 600 Ω (20 mA)
Behavior in the event of a sensor erroraccording to NE 43 or freely configurable
Output nameRelay output
Contact type1 PDT
Contact materialAgSnO2, hard gold-plated
Maximum switching voltage30 V AC (30 V DC)
Maximum inrush current0.5 A (30 V AC)
1 A (30 V DC)

Power supply

Supply voltage range24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Power consumption< 1.5 W

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length7 mm
Screw threadM3
Connection methodScrew connection

General

Maximum temperature coefficient0.01 %/K
Flammability rating according to UL 94V0
Degree of pollution2
Overvoltage categoryII
Electromagnetic compatibilityConformance with EMC directive
Housing materialPA 66-FR
Colorgreen
DesignationInput/output/power supply
Electrical isolation300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
DesignationInput/output
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
DesignationInput/power supply
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
DesignationInput/switching output
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
ConformanceCE-compliant
ATEX II 3 G Ex nA nC ic IIC T4 Gc X
IECExEx nA nC ic IIC T4 Gc X
UL, USA / CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Functional Safety (SIL)SIL 2

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Electrical isolation4-way, between input/output/power supply/switching output
Flammability rating according to UL 94V0
ConformanceCE-compliant
ATEX II 3 G Ex nA nC ic IIC T4 Gc X
IECExEx nA nC ic IIC T4 Gc X
UL, USA / CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6

eCl@ss

eCl@ss 4.027210107
eCl@ss 4.127210107
eCl@ss 5.027210107
eCl@ss 5.127210107
eCl@ss 6.027210107
eCl@ss 7.027210107
eCl@ss 8.027371503

ETIM

ETIM 4.0EC001596
ETIM 5.0EC002568

UNSPSC

UNSPSC 6.0130211506
UNSPSC 7.090139121008
UNSPSC 1139121008
UNSPSC 12.0139121008
UNSPSC 13.239121008

ETIM for 2811394 Sensors (EC002919)
Feature Name Feature Value
Measuring range (EF001836) -250 °C
Analogue output 0 mA ... 20 mA (EF006808) No
Analogue output 4 mA ... 20 mA (EF006810) Yes
Analogue output 0 V ... 2 V (EF009886) No
Analogue output 0 V ... 5 V (EF009887) No
Analogue output 0 V ... 10 V (EF006807) No
Analogue output 2 V ... 10 V (EF009888) No
With switching output (EF005225) Yes
EMC-version (EF001062) Yes
Ambient temperature (EF002386) 65 °C
Weight (EF000167) 0.1939 kg

Datasheet - PDF

Reviews (1)

  • Marko
    Customer rating:
  • Page:1
    Add Review
    hide form
    Rating:
    Name:
    Email:
    Subject:
    Text:
      Captcha
      Add review

    All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.