Surge protection device
Terminal block with surge voltage fine protection between clamping connector and DIN rail, nominal voltage: 12 V DC, for mounting on NS 32 or NS 35/7.5, terminal width: 6.2 mm, terminal height: 47 mm
Trabtech (TT)
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Product type | Surge protection for MCR technology |
| IEC test classification | C1 |
| C3 | |
| VDE requirement class | C1 |
| C3 | |
| Type | Single-level terminal block |
| Number of positions | 1 |
| Surge protection fault message | none |
| Nominal voltage UN | 12 V DC |
| Connection method | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Conductor cross section flexible | 0.2 mm² ... 4 mm² |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Width | 6.2 mm |
| Height | 42.5 mm |
| Depth | 47 mm |
| Flammability rating according to UL 94 | V-2 |
| Housing material | PA |
| Mechanical data | |
| Open side panel | Yes |
| Direction of action | Line-Earth Ground |
| Maximum continuous voltage UC | 13 V DC |
| 9 V AC | |
| Rated current | 32 A (50 °C) |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs (line-ground) | 346 A (per path) |
| Total surge current (8/20) µs | 346 A |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 346 A |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 67 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 19 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 19 V |
| Residual voltage at In(conductor-ground) | ≤ 20 V |
| Response time tA(line-earth) | ≤ 1 ns |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system | typ. 1 MHz |
| Capacity (Core-Earth) | ≤ 2.35 nF |
| Surge protection fault message | none |
| Impulse durability (line-earth) | C1 - 500 V / 250 A |
| C3 - 25 A |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| VDE requirement class | C1 |
| C3 | |
| Standards Information technology specification | |
| Standards/regulations | IEC 61643-21 |
| IEC 61643-21 | |
| Standards/specifications | IEC 61643-21 |
| Note | 2000 |
| Mounting type | DIN rail: 35 mm |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG PHOENIX PROTECTION EN .pdf | 27 Mbytes |
|
| PHOENIX CONTACT-2794686-TT-UK5/ 12DC | 142 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.