TT-SLKK5/ 60AC 2794974 PHOENIX CONTACT Modular terminal block with varistor as surge voltage protection betw.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

TT-SLKK5/ 60AC 2794974 PHOENIX CONTACT Modular terminal block with varistor as surge voltage protection betw..

TT-SLKK5/ 60AC

2794974

PHOENIX_CONTACT

50

Available

Ship on today

Modular terminal block with varistor as surge voltage protection between clamping connector and DIN rail, separate ground connection, nominal voltage: 60 V AC, mounting on NS 35/7.5, terminal width: 6.2 mm, terminal height: 69 mm

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection for measurement and control technology - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
50+$14.25
100+$14.16
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Height69.5 mm
Width6.2 mm
Length66.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialPA
Flammability rating according to UL 94V2
Colorblack
Mounting typeDIN rail: 35 mm
TypeSingle-level terminal block – separate PE connection
Number of positions1
Direction of actionLine-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
VDE requirement classC1
C2
C3
Nominal voltage UN60 V AC
Maximum continuous voltage UC100 V DC
75 V AC
Maximum continuous voltage UC (wire-ground)100 V DC
75 V AC
Nominal current IN32 A (50 °C)
Operating effective current IC at UC≤ 50 µA
Residual current IPE≤ 50 µA
Nominal discharge current In (8/20) µs (Core-Earth)2 kA
Total surge current (8/20) µs6.5 kA
Max. discharge current Imax (8/20) µs maximum (Core-Earth)6.5 kA
Nominal pulse current Ian (10/1000) µs (Core-Earth)75 A
Output voltage limitation at 1 kV/µs (Core-Earth) spike≤ 180 V
Output voltage limitation at 1 kV/µs (Core-Earth) static≤ 180 V
Residual voltage at In (conductor-ground)≤ 315 V
Response time tA (Core-Earth)≤ 25 ns
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm systemtyp. 1.1 MHz

Connection data

Connection methodScrew connection
Connection type INScrew terminal blocks
Connection type OUTScrew terminal blocks
Screw threadM3
Tightening torque0.5 Nm
Stripping length8 mm
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.4 mm²
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12

Standards and Regulations

Standards/regulationsIEC 61643-21

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2794974-TT-SLKK5/ 60AC English 110 Kbytes PHOENIX CONTACT-2794974-TT-SLKK5/ 60AC

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Últimas Opiniones de Nuestros Clientes

Todas las valoraciones que recibimos de los artículos que ofrecemos son reales y están verificadas. Un pequeño gesto, pero de mucho valor. Por eso, te agradecemos ese minuto que inviertes en dejarnos tu opinión y calificación sobre los productos, porque nos ayuda a seguir mejorando y a ofrecerte un servicio de todavía mayor calidad.