Orderkey | 2839570 |
---|---|
Packing unit | 10 pc |
Catalog page | Page 161 (C-4-2017) |
GTIN | 4017918591113 |
Weight per Piece (excluding packing) | 22.150 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
Housing material | PA |
---|---|
Flammability rating according to UL 94 | V-0 |
Color | black |
Standards for cearances and creepage distances | DIN VDE 0110-1 |
IEC 60664-1 | |
Mounting type | on base element |
Type | Male |
Number of positions | 5 |
Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 | |
VDE requirement class | C1 |
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 12 V DC |
Maximum continuous voltage UC | 13 V DC |
9 V AC | |
Rated current | 450 mA (45°C) |
Operating effective current ICat UC | ≤ 5 µA |
Residual current IPE | ≤ 4 µA (with PT 2X2-BE) |
≤ 1 µA (with PT 2X2+F-BE) | |
Nominal discharge current In(8/20) µs (line-line) | 10 kA |
Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
Pulse discharge current Iimp(10/350) µs | 2.5 kA |
Total discharge current Itotal(8/20) µs | 20 kA |
Max. discharge current Imax(8/20) µs maximum (line-line) | 10 kA |
Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA |
Nominal pulse current Ian (10/1000) µs (line-line) | 67 A |
Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 50 V |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V |
≤ 1 kV (with PT 2X2+F-BE) | |
Output voltage limitation at 1 kV/µs (line-line) static | ≤ 25 V |
Output voltage limitation at 1 kV/µs (line-signalground) static | ≤ 450 V |
Residual voltage at In(line-line) | ≤ 25 V |
Residual voltage with Ian (10/1000) µs (line-line) | ≤ 23 V |
Voltage protection level Up(line-line) | ≤ 100 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up(line-earth) | ≤ 450 V (C2 - 10 kV / 5 kA) |
Response time tA(line-line) | ≤ 500 ns |
Response time tA(line-earth) | ≤ 500 ns |
Input attenuation aE, sym. | 0.2 dB (≤ 5 MHz) |
Input attenuation aE, asym. | |
Cut-off frequency fg (3 dB), sym. in 100 Ohm system | typ. 70 MHz |
Capacity (line-line) | typ. 30 pF |
Resistance in series | 2.2 Ω |
Surge protection fault message | none |
Max. required back-up fuse | 500 mA (T) |
Impulse durability (line-line) | C2 - 10 kV/5 kA |
Impulse durability (line-earth) | C2 - 10 kV/5 kA |
D1 - 2.5 kA |
Connection method | Screw connection (in connection with the base element) |
---|---|
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section solid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX PROTECTION EN.pdf | 27 Mbytes | |
PHOENIX CONTACT-2839570-PT 2X2-HF-12 DC-ST | 145 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.