PT 2-IT-230AC-ST 2805127 PHOENIX CONTACT Type 3 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PT 2-IT-230AC-ST 2805127 PHOENIX CONTACT Type 3 surge protection plug

PT 2-IT-230AC-ST

2805127

PHOENIX_CONTACT

Type 3 surge protection plug

Surge protection plug for base element, as device protection for termination devices in IT systems, error indication in the connector. Design: 230 V AC

More details


Home > PHOENIX CONTACT

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete.

Go to successor article: PLT-T3-IT-230-P 2906451

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Technical data

Product properties
Product typeDevice protection
TypeMale
Number of positions2
Surge protection fault messageoptical
IEC test classificationIII
T3
EN typeT3

Dimensions
Dimensional drawingpcpjkmlape.jpg
Width17.7 mm
Height45 mm
Depth52 mm
Horizontal pitch1 Div.
Complete module width17.7 mm
Complete module height90 mm
Complete module depth65.5 mm

Material specifications
Flammability rating according to UL 94V0
Housing materialPA

Protective circuit
Direction of action1L-N & N-PE
Nominal frequency fN50 Hz
60 Hz
Maximum continuous voltage UC275 V AC
Maximum continuous operating voltage UC(L-N)275 V AC
Maximum continuous operating voltage UC(L-PE)275 V AC
Maximum continuous operating voltage UC(N-PE)275 V AC
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs3 kA
3 kA (in acc. with UL 1449)
Nominal discharge current In(8/20) µs (L-N)3 kA
Nominal discharge current In(8/20) µs (L-PE)3 kA
Maximum discharge current Imax(8/20) µs8 kA
Energy absorption symmetrical170 J (L-N)
Enery absorption, asymmetrical225 J (L/N-PE)
Voltage protection level Up(L-N)≤ 1.2 kV
Voltage protection level Up(L-PE)≤ 1.5 kV
Voltage protection level Up(N-PE)≤ 1.5 kV
Response time tA(L-N)≤ 25 ns
Response time tA(L-PE)≤ 100 ns
Response time tA(N-PE)≤ 100 ns
Max. required back-up fuse25 A (gL/C)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 75 °C

Standards and regulations
Air clearances and creepage distances
Standards/regulationsIEC 60664-1 / IEC 61643-1 / DIN EN 61643-11/A11
Standards
Standards/regulationsIEC 61643-1
EN 61643-11/A11
IEC 61643-1
EN 61643-11/A11
Standards/specificationsIEC 61643-1
Note2005
Standards/specificationsEN 61643-11/A11
Note2007

Mounting
Mounting typeon base element

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.