Product successfully added to your shopping cart
PT 2-F-ST
2859000
PHOENIX_CONTACT
1
Surge protection plug
Plug-in surge protection for the base element, surge protection for two signal cables grounded on one side.
Trabtech (TT)
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Orderkey | 2859000 |
|---|---|
| Packing unit | 10 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 115 (C-4-2017) |
| GTIN | 4017918902452 |
| Weight per Piece (excluding packing) | 16.120 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
| Height | 45 mm |
|---|---|
| Width | 17.7 mm |
| Depth | 52 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Mounting type | on base element |
| Type | Male |
| Direction of action | Line-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.10 |
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 48 V AC |
| Maximum continuous voltage UC | 60 V DC |
| 48 V AC | |
| Rated current | 2 A AC (80 °C) |
| 150 mA DC (80 °C) | |
| Operating effective current ICat UC | ≤ 2 µA |
| Residual current IPE | ≤ 4 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 20 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 5 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 600 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 25 V |
| Voltage protection level Up(line-earth) | ≤ 600 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Upstatic (line-earth) | ≤ 25 V (C2 - 10 kV / 5 kA) |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, asym. | typ. 0.1 dB (≤ 1 MHz / 50 Ω) |
| Cut-off frequency fg (3 dB), asym. (GND) in 50 Ohm system | typ. 100 MHz |
| Capacity (line-earth) | typ. 2 pF |
| Resistance in series | 0 Ω |
| Surge protection fault message | none |
| Max. required back-up fuse | 2 A AC (T) |
| 150 mA DC (T) | |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| C1 - 1 kV/500 A | |
| C3 - 100 A | |
| D1 - 2.5 kA |
| Connection method | Screw connection (in connection with the base element) |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |
| Feature Name | Feature Value |
|---|---|
| Nominal voltage DC (EF008799) | 48 V |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG PHOENIX PROTECTION EN .pdf | 27 Mbytes |
|
| PHOENIX CONTACT-2859000-PT 2-F-ST | 123 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.