VAL-MS 400 ST 2816399 PHOENIX CONTACT Surge protection connector type 2 with high-capacity varistor for VAL-.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MS 400 ST 2816399 PHOENIX CONTACT Surge protection connector type 2 with high-capacity varistor for VAL-..

VAL-MS 400 ST

2816399

PHOENIX_CONTACT

10

Available

Ship on today

Surge protection connector type 2 with high-capacity varistor for VAL-MS base element, thermal monitoring, visual fault warning. Design: 400 V AC

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
10+37,42 €
20+36,70 €
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g
Vibration (operation)5g

General

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012
IEC test classificationII
T2
EN typeT2
IEC power supply systemTN
TT
IT
SPD designVoltage-limiting type
Mode of protectionL-PEN
L-N
L-PE
Mounting typeOn base element
Colorblack
Housing materialPA 6.6
Pollution degree2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions1
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.10
Surge protection fault messageoptical

Additional descriptions

NoteUsable in all low-voltage systems between L-N or L-PEN.Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a)

Protective circuit

Nominal voltage UN240/415 V AC (TN)
240/415 V AC (TT)
230 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC440 V AC
Residual current IPE≤ 0.45 mA
Standby power consumption PC≤ 200 mVA
Nominal discharge current In (8/20) µs20 kA
Maximum discharge current Imax (8/20) µs40 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 2.2 kV
Residual voltage Ures≤ 2.2 kV (at In)
≤ 1.8 kV (at 10 kA)
≤ 1.5 kV (at 5 kA)
≤ 1.4 kV (at 3 kA)
TOV behavior at UT440 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring125 A AC (gG)

Connection data

Connection methodVALVETRAB plug-in system

UL specifications

SPD Type4 (for Type 2 applications)
Maximum continuous operating voltage MCOV (L-N)440 V AC
Nom. voltage400 V AC
Mode of protectionL-N
Power distribution system1
Nominal frequency50/60 Hz
Voltage protection rating VPR (L-N)1.5 kV
Nominal discharge current In (L-N)20 kA

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2816399-VAL-MS 400 STEnglish123 KbytesPHOENIX CONTACT-2816399-VAL-MS 400 ST

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review