S-PT-EX-24DC 2800034 PHOENIX CONTACT Surge protection for one floating signal circuit in screw-on module wit.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

S-PT-EX-24DC 2800034 PHOENIX CONTACT Surge protection for one floating signal circuit in screw-on module wit..

S-PT-EX-24DC

2800034

PHOENIX_CONTACT

Available

Ship on today

Surge protection for one floating signal circuit in screw-on module with IP67 protection for sensor heads, connection M20 x 1.5. Tested in acc. with the protection types in Ex areas Ex d / Ex tD / Ex ia IIC / Ex iaD.

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection for measurement and control technology - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+113,97 €
2+110,77 €
4+108,17 €
5+107,44 €
7+106,60 €
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Height28 mm
Width28 mm
Depth79 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 80 °C (non-Ex)
Degree of protectionIP67

General

Housing materialHigh-grade steel
Colorsilver
Standards for cearances and creepage distancesIEC 60664-1
IEC 60079-11
Mounting typeM20
TypeScrew-in module
Number of positions2
Direction of actionLine-Line & Line-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC36 V DC
25 V AC
Maximum continuous voltage UC (wire-wire)36 V DC
25 V AC
Residual current IPE≤ 2 µA
Nominal discharge current In (8/20) µs (Core-Core)260 A
Nominal discharge current In (8/20) µs (Core-Earth)10 kA
Total surge current (8/20) µs20 kA
Total surge current (10/350) µs2 kA
Nominal pulse current Ian (10/1000) µs (Core-Core)50 A
Impulse discharge current (10/350)˽µs, peak value limp1 kA
Output voltage limitation at 1 kV/µs (Core-Core) spike≤ 130 V
Output voltage limitation at 1 kV/µs (Core-Earth) spike≤ 1.1 kV
Output voltage limitation at 1 kV/µs (Core-Core) static≤ 60 V
Voltage protection level Up (core-core)≤ 65 V (C3 - 10 A)
Voltage protection level Up (core-ground)≤ 1.1 kV (C3 - 100 A)
≤ 1.1 kV (C1 - 1 kV/500 A)
≤ 1.2 kV (C2 - 10 kV / 5 kA)
Response time tA (Core-Core)≤ 1 ns
Response time tA (Core-Earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.1 dB (30 MHz / 50 Ω)
typ. 0.1 dB (6 MHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm systemtyp. 70 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 40 MHz
Capacity (Core-Core)typ. 20 pF
Capacity (Core-Earth)typ. 5 pF
Surge protection fault messageNone
Impulse durability (conductor-conductor)C3 - 25 A
Impulse durability (conductor-ground)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 100 A
D1 - 1kA
Alternating current carrying capacity (conductor-ground)10 A - 1 s

Connection data

Connection methodIndividual wires

Standards and Regulations

Standards/regulationsEN 61643-21
EN 60079-0
EN 60079-1
EN 60079-11
EN 60079-26
EN 61241-0
EN 61241-1
EN 61241-11

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2800034-S-PT-EX-24DCEnglish187 KbytesPHOENIX CONTACT-2800034-S-PT-EX-24DC