Surge protection device
Two-level surge protection for three or four potential-free driven signal circuit signals to ground on the IP67 rated spin-on module for sensor heads, 1/2 in. 14 NPT. Tested according to the types of protection in the Ex Ex d/Ex tD/Ex ia IIC/Ex iaD zones. Suitable for use in fieldbus systems according to the FISCO concept (intrinsically safe bus concept), suitable for HART.
Two-stage surge protection for three or four signals of floating signal circuits in the screw-on module with IP67 degree of protection for sensor heads, connection ½-inch 14 NPT. Tested in accordance with the following types of protection in Ex areas: Ex d/Ex tD/Ex ia IIC/Ex iaD. Suitable for use in the fieldbus system in accordance with the FISCO concept, HART-compatible. Can be used in safety-related circuits up to SIL 3.
Earthing, lightning and surge protection > Combined arrester for data networks/MCR-technology
Trabtech (TT)
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Product type | Surge protection for MCR technology |
| Product family | SURGETRAB |
| IEC test classification | C1 |
| C2 | |
| C3 | |
| D1 | |
| Type | Screw-in module |
| Number of positions | 4 |
| Data management status | |
| Article revision | 08 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal voltage UN | 24 V DC |
| Connection method | Individual wires |
| Maximum inner capacitance Ci | 1.65 nF |
| Max. internal inductance Li | 1 µH |
| Max. input current Ii | 500 mA (T4 / ≤ 75 °C) |
| 500 mA (T5 / ≤ 75 °C) | |
| 500 mA (T6 / ≤ 60 °C) | |
| Max. input voltage Ui | 36 V DC |
| max. input power Pi | 3.00 W |
| Insulation voltage to ground | 500 V AC |
| Ambient temperature (operation) | -40 °C ... 75 °C (T4) |
| -40 °C ... 75 °C (T5) | |
| -40 °C ... 60 °C (T6) | |
| Operating temperature range | -40 °C ... 100 °C (T4) |
| -40 °C ... 75 °C (T5) | |
| -40 °C ... 60 °C (T6) | |
| Max. surface temperature | 135 °C (T4) |
| 100 °C (T5) | |
| 85 °C (T6) |
| Dimensional drawing | ![]() |
| Width | 28 mm |
| Height | 28 mm |
| Depth | 79 mm |
| Color | Steel/stainless steel color |
| Housing material | Stainless steel 1.4404 |
| ASTM 316L |
| Mechanical data | |
| Open side panel | No |
| Direction of action | Line-Line & Line-Earth Ground |
| Maximum continuous voltage UC | 36 V DC |
| 25 V AC | |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-line) | 260 A |
| Nominal discharge current In(8/20) µs (line-ground) | 10 kA |
| Pulse discharge current Iimp(10/350) µs | 1 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Total discharge current Itotal(10/350) µs | 2 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 50 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 130 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 1.1 kV |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 60 V |
| Voltage protection level Up(line-line) | ≤ 65 V (C3 - 10 A) |
| Voltage protection level Up(line-earth) | ≤ 1.1 kV (C3 - 100 A) |
| ≤ 1.1 kV (C1 - 1 kV / 500 A) | |
| ≤ 1.2 kV (C2 - 10 kV / 5 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.1 dB (30 MHz / 50 Ω) |
| typ. 0.1 dB (6 MHz / 150 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 50 Ω system | typ. 70 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ω system | typ. 70 MHz |
| Capacity (Core-Core) | typ. 20 pF |
| Capacity (Core-Earth) | typ. 5 pF |
| Surge protection fault message | none |
| Impulse durability (line-line) | C3 - 25 A |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 1 kA | |
| Alternating current carrying capacity (line-earth) | 10 A - 1 s |
| Ambient conditions | |
| Degree of protection | IP67 |
| Ambient temperature (operation) | -40 °C ... 80 °C (non-Ex) |
| Altitude | ≤ 2000 m (amsl) |
| Conformity/Approvals | |
| ATEX | II 1 G Ex ia IIC T4...T6 |
| II 2 G Ex d IIC T4...T6 | |
| II 1 D Ex iaD 20 IP6x T85 °C...135 °C | |
| II 2 D Ex tD A21 IP6x T85 °C...135 °C | |
| IECEx | Ga Ex ia IIC T4...T6 |
| Ex d IIC T4...T6 | |
| Ex iaD IP6x T85 °C...135 °C | |
| Ex tD A21 IP6x T85 °C...135 °C | |
| Air clearances and creepage distances | |
| Standards/regulations | IEC 60664-1 / IEC 60079-11 |
| Standards/specifications | EN 61643-21 |
| Note | A2:2013 |
| Standards/specifications | EN 60079-0 |
| Note | 2018 |
| Standards/specifications | EN 60079-1 |
| Note | 2007 |
| Standards/specifications | EN 60079-11 |
| Note | 2012 |
| Standards/specifications | EN 60079-31 |
| Note | 2009 |
| Standards/specifications | IEC 60079-0 |
| Note | 2017 |
| Standards/specifications | IEC 60079-1 |
| Note | 2007 |
| Standards/specifications | IEC 60079-11 |
| Note | 2011 |
| Standards/specifications | IEC 60079-31 |
| Note | 2008 |
| Mounting type | 1/2" NPT |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG PHOENIX PROTECTION EN .pdf | 27 Mbytes |
|
| PHOENIX CONTACT-2800037-S-PT-4-EX-24DC-1/2" | 131 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.