Surge protection, consisting of plug-in protection and base element, with multi-level status indication integrated into the module for two floating 2-wire signal circuits. Indirect earthing by gas discharger, suitable for HART.

Surge protection, consisting of protective plug and base element, with integrated multi-stage status indicator on the module, for two 2-wire floating signal circuits. Indirect grounding via gas discharge tube, HART-compatible. Can be used in safety-related circuits up to SIL 3.

More details


Earthing, lightning and surge protection > Surge protection device for data networks/MCR-technology

Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $474.39
Unit price: $474.39
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Technical data

Notes
General
NoteRemote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.

Product properties
Product typeSurge protection for MCR technology
Product familyPLUGTRAB IQ
IEC test classificationC1
C2
C3
D1
TypeDIN rail module, two-section, divisible
Surge protection fault messageOptical, multi-stage
Wire pairs per module2
Data management status
Article revision08
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal voltage UN24 V DC

Connection data
Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section rigid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Dimensions
Dimensional drawingdjskbjiuwq.jpg
Width17.7 mm
Height91 mm
Depth77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Material specifications
Colorblack (RAL 9005)
black (RAL 9005)
Flammability rating according to UL 94V-0
Housing materialPA 6.6

Mechanical properties
Mechanical data
Open side panelNo

Protective circuit
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC30 V DC
21 V AC
Rated current700 mA (50 °C)
Operating effective current ICat UC≤ 1 mA (in the signal circuit)
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (line-line)10 kA
Nominal discharge current In(8/20) µs (line-ground)10 kA
Pulse discharge current Iimp(10/350) µs (line-earth)2.5 kA
Total discharge current Itotal(8/20) µs20 kA
Voltage protection level Up(line-line)≤ 80 V (C1 - 1 kV / 500 A)
≤ 130 V (C2 - 10 kV / 5 kA)
≤ 150 V (C2 - 10 kA)
≤ 55 V (C3 - 25 A)
≤ 60 V (C3 - 100 A)
Voltage protection level Up(line-earth)≤ 900 V (C1 - 1 kV / 500 A)
≤ 1300 V (C2 - 10 kV / 5 kA)
≤ 1200 V (C2 - 10 kA)
≤ 1000 V (C3 - 25 A)
≤ 1300 V (C3 - 100 A)
Voltage protection level Up(line-signalground)≤ 600 V (C1 - 1 kV / 500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 800 V (C2 - 10 kA)
≤ 700 V (C3 - 25 A)
≤ 800 V (C3 - 100 A)
Voltage protection level Upstatic (line-line)≤ 65 V (C1 - 1 kV / 500 A)
≤ 65 V (C2 - 10 kA)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Response time tA(line-signalground)≤ 100 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 270 kHz/150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ω systemtyp. 1.1 MHz
Capacity (Core-Earth)typ. 2 nF
Resistance per path1.2 Ω ±5 %
Surge protection fault messageOptical, multi-stage
Max. required back-up fuse800 mA (FF)
Impulse durability (line-line)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C2 - 10 kA
C3 - 100 A
Impulse durability (line-earth)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C2 - 10 kA
C3 - 100 A
D1 - 2.5 kA
Impulse durability (line-signalground)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C2 - 10 kA
C3 - 100 A
D1 - 2,5 kA
Pulse reset time (line-line)≤ 4000 ms
Pulse reset time (line-earth)≤ 30 ms
Pulse reset time (line-signalground)≤ 2600 ms

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl)
Permissible humidity (operation)5 % ... 95 %

Standards and regulations
Standards/specificationsIEC 61643-21
Note2000 + A1:2008, modified
Standards/specificationsEN 61643-21
Note2001 + A1:2009
Standards/specificationsEN 61000-6-3
Note2007 + A1:2011
Standards/specificationsEN 61000-6-2
Note2005

Mounting
Mounting typeDIN rail: 35 mm

ETIM for 2800981 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage DC (EF008799) 24 V

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.