CT 10-18FS+F/PE-24 2807926 PHOENIX CONTACT LSA-PLUS plug (COMTRAB CT 10) with surge voltage coarse and fine .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

CT 10-18FS+F/PE-24 2807926 PHOENIX CONTACT LSA-PLUS plug (COMTRAB CT 10) with surge voltage coarse and fine ..

CT 10-18FS+F/PE-24

2807926

PHOENIX_CONTACT

Available

Ship on today

LSA-PLUS plug (COMTRAB CT 10) with surge voltage coarse and fine protection for 18 signal lines - GND and coarse protection GND - PE. Nominal voltage: 24 V DC/AC. Design: 10 double wires

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection for information technology - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
1+$525.49
2+$508.61
3+$501.38
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Height22 mm
Width111 mm
Depth68.5 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 75 °C
Degree of protectionIP20

General

Housing materialPBT
Flammability rating according to UL 94V0
Colorblack
Standards for cearances and creepage distancesVDE 0110-1
Mounting typeOn CT-TERMIBLOCK and LSA-PLUS disconnect strip
TypeLSA-PLUS module
Direction of actionLine-Signal Ground/Shield & Signal Ground/Shield-Earth Ground
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.00

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC40 V DC
28 V AC
Maximum continuous voltage UC (wire-GND)40 V DC
28 V AC
Nominal current IN1.5 A (75°C)
Operating effective current IC at UC5 µA (18x)
Residual current IPE≤ 1 µA
Nominal discharge current In (8/20) µs (Core-Core)214 A (25 °C)
Nominal discharge current In (8/20) µs (Core-Earth)5 kA
Total surge current (8/20) µs10 kA
Max. discharge current Imax (8/20) µs119 A (25 °C)
Output voltage limitation at 1 kV/µs (Core-Earth) spike≤ 60 V
Output voltage limitation at 1 kV/µs (Core-Earth) static≤ 650 V
Residual voltage at In (conductor-conductor)≤ 85 V (a-b)
Residual voltage at In (conductor-GND)≤ 85 V
Residual voltage with Ian (10/1000)µs (conductor-GND)≤ 65 V
Response time tA (Core-Core)≤ 1 ns (a-b)
Response time tA (Core-Earth)≤ 100 ns (a, b)
Cut-off frequency fg (3 dB), sym. in 50 Ohm system10 MHz (typical)
Cut-off frequency fg (3 dB), sym. in 150 Ohm system2.5 MHz (typical)
Capacity (Core-Earth)1.1 nF (1 MHz a-b)
Surge protection fault messageNone
Impulse durability (conductor-ground)D1 - 2,5 kA
Impulse durability (GND-Ground)D1 - 2.5 kA

Connection data

Connection methodcan be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips
Connection type INCOMTRAB plug-in system
Connection type OUTCOMTRAB plug-in system

Standards and Regulations

Standards/regulationsIEC 61643-21

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2807926-CT 10-18FS+F/PE-24 English 151 Kbytes PHOENIX CONTACT-2807926-CT 10-18FS+F/PE-24

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.