MNT-TV-SAT D/WH 2882297 PHOENIX CONTACT Socket attachment plug with surge protection for the power supply un.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MNT-TV-SAT D/WH 2882297 PHOENIX CONTACT Socket attachment plug with surge protection for the power supply un..

MNT-TV-SAT D/WH

2882297

PHOENIX_CONTACT

Socket attachment plug with surge protection for the power supply unit and signal connection for radio and television equipment (cable, terrestrial antenna, satellite system). Cable is provided.

Surge protected power outlet adapter for power supply and connection of radio and TV signals (cable, terrestrial antenna, satellite installation). The cable is included.

More details


Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Technical data

Notes
General
NoteShielding requirements according to DIN EN 50083-2, Class A

Product properties
Product typeDevice protection
Product familyMAINTRAB
IEC test classificationC2
C3
D1
IEC power supply systemTN
TT
TypeAttachment plug
Number of positions2
For country-specific use inD, A, NL, E, S, FIN, TR
Surge protection fault messageoptical
Data management status
Article revision12
Insulation characteristics
Overvoltage categoryII
Pollution degree2
IEC test classificationIII
T3
EN typeT3
Number of portsOne

Connection data
Connection methodF connector
Connection methodGrounding plug/socket

Dimensions
Dimensional drawingnbvjaniftc.jpg
Width63 mm
Height107 mm
Depth78 mm

Material specifications
Colorwhite (RAL 9010)
black (RAL 9005)
Flammability rating according to UL 94V-0
CTI value of material400
600
Insulating materialPA 6
Housing materialPA 6

Protective circuit
Power supplies
Direction of actionL/N-PE & Signal Line-Shield-Earth Ground
Nominal voltage UN230/400 V AC (TN/TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC(L-N)275 V AC
Maximum continuous operating voltage UC(L-PE)360 V AC
Maximum continuous operating voltage UC(N-PE)360 V AC
Rated load current IL16 A (30 °C)
Residual current IPE≤ 5 µA
Standby power consumption PC≤ 1 VA
Reference test voltage UREF255 V AC
Combination wave UOC6 kV
Voltage protection level Up≤ 1.5 kV
TOV behavior at UT(L-N)460 V AC (5 s / withstand mode)
460 V AC (120 min / safe failure mode)
TOV behavior at UT(L-PE)460 V AC (5 s / withstand mode)
460 V AC (120 min / withstand mode)
1455 V AC (200 ms / safe failure mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / safe failure mode)
Response time tA(L-N)≤ 25 ns
Response time tA(L-PE)≤ 100 ns
Response time tA(N-PE)≤ 100 ns
Max. required back-up fuse16 A (gG / B / C)
Short-circuit current rating ISCCR1.5 kA AC
Information technology
Maximum continuous voltage UC24 V DC
Rated current1.5 A (25 °C)
Operating effective current ICat UC≤ 1 µA
Standby power consumption PC≤ 1 VA
Residual current IPE≤ 1 µA
Insulation resistance Riso≥ 70 MΩ
≥ 70 MΩ
Nominal discharge current In(8/20) µs (line-ground)2.5 kA
Nominal discharge current In(8/20) µs (line-shield)2.5 kA
Nominal discharge current In(8/20) µs (shield-ground)5 kA
Total discharge current Itotal(8/20) µs5 kA
Nominal pulse current Ian (10/1000) µs (line-shield)120 A
Nominal pulse current Ian (10/1000) µs (shield-ground)200 A
Output voltage limitation at 1 kV/µs (line-shield) spike≤ 700 V
Output voltage limitation at 1 kV/µs (shield-ground) spike≤ 1 kV
Output voltage limitation at 1 kV/µs (line-shield) static≤ 700 V
Output voltage limitation at 1 kV/µs(shield-ground) static≤ 1 kV
Residual voltage at In(conductor-shield)≤ 40 V
Residual voltage at In(shield-ground)≤ 50 V
Voltage protection level Up(line-shield)≤ 700 V (C2 - 2 kA)
Voltage protection level Up(shield-ground)≤ 1.2 kV (C2 - 5 kA)
Response time tA (line-shield)≤ 100 ns
Response time tA (shield-ground)≤ 100 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 2.4 GHz /75 Ω)
Cut-off frequency fg (3 dB), asym. (shield) in 75 Ω systemtyp. 2.5 GHz
Frequency range0 Hz ... 2400 MHz
Capacity asymmetrical (shield)typ. 10 pF
Alternating current carrying capacity (line-shield)5 A - 1 s
Alternating current carrying capacity (shield-ground)10 A - 1 s
Pulse reset time (line-shield)≤ 4 s

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20 (Child-proofing)
Ambient temperature (operation)-25 °C ... 75 °C
Ambient temperature (storage/transport)-25 °C ... 75 °C
Altitude≤ 2000 m (amsl)
Permissible humidity (operation)5 % ... 95 %

Standards and regulations
Standards/specificationsIEC 61643-11
Note2011
Standards/specificationsEN 61643-11
Note2019
Standards/specificationsEN 61643-21
NoteA2:2013
Standards/specificationsIEC 61643-21
NoteA2:2012
Standards/specificationsEN 50083
NoteCLASS-A

Mounting
Mounting typePlugging into the mains socket

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.